5.4. Operating conditions.
Ambient temperature range
-40°C
85°C
Operating temperature for intrinsic-safe versions
(Exi) in
accordance with „Appendix Exi”.
Operating temperature for Exd versions
in accordance
with „Appendix Exd.01”.
Relative humidity
up to 98%
Medium temperature range
Pt100
- 200 ... 550 °C
N-Cr-NiAl - 40 ... 550 °
C
Thermal compensation range
-
25 … 75
0
C
5.4.1. Electromagnetic Compatibility (EMC), immunity
Rating according to EN 61326-1,2for industrial applications
Electrostatic Discharge Immunity (ESD):
EN 61000-4-2; S3 level: contact ±6kV, air ±8kV; criterion A
Conducted Radio Frequency:
EN 61000-4-
6; 0,15… 80MHz, 10V; criterion A
Radiated electromagnetic Field:
EN 61000-4-
3; 80… 2 000MHz – 10V/m, 2 000 … 2 700MHz – 1V/m; criterion A
Electrical Fast Transient (Burst Immunity)
EN 61000-4-4; ± 2kV power supply port/earth, ± 1kV signal port/earth; criterion A
Electrical Slow Transient (Surge Immunity):
EN 61000-4-5; ±0.5kV (±1kV) 0,5kV differentia mode, 1kV common mode; criterion B
5.4.2. Electromagnetic Compatibility, emission:
According to CISPR16-1, CISPR 16-2, class B, distance to the antenna 3m, quasi-peak measuring:
Radiated emission:
0,15 … 30MHz, 80-52dBμV/m;
30 … 2000MHz, <54dBμV/m
Conducted emission:
0,01 … 0,150MHz, 96-50dBμV/m;
0,150 … 0,350MHz, 60-50dBμV/m;
0,35 … 30MHz, <50dBμV/m
5.4.3. Climatic immunity: dry heat, cold, humidity, salt mist:
Dry heat:
EN 60068-2-2, test B; T = 70
0
C, RH = max 55%
Cold :
EN 60068-2-1, test A; T = -25
0
C,
Damp heat cycle:
EN 60068-2-30, test D ; (T = 55
0
C, RH = min95%, 24h)x2
5.4.4. Mechanical immunity
Shocks:
EN 60068-2-27, 50g/11ms
Vibrations:
EN 60068-2-6, test Fc; up to
1,6mm for 2 … 25Hz, up to 4g for 25 … 100Hz