9 IOM-DPT-A: FEB 2014

Appendix Exi


5.4.
Input inductance and capacity: Ci = 20nF, Li = 1,1mH

5.5. Supply voltage min.: 13.5VDC **

5.6. Load resistance:

from 28V linear supply

Ro max [Ω] = for transmitter without display back lighting

from a source with “trapezial” or “rectangular” characteristic supply

Ro

max [Ω] =

*) barrier resistance
**) 16,5V for transmitter with display back lighting

5.7. Temperature


Temperature of transmitter’s surface from regard temperature of shield part as on figure in point 2.3. can't
surpass the admissible values of temperatures for temperature class of steam and gases according with
standard PN-EN 60079-0.
Simultaneously the casing temperature should not surpass max. temperature value Ta definite for
conditions power supply in Certificate Exi and p.5 of Appendix Exi.

6.

How to connect Ex transmitters DPT-2000ALW.

The transmitter and other devices in the measuring loop should be connected in accordance
with the intrinsic-safety and explosion-safety regulations and the conditions for use in
dangerous areas.

Failure to observe the intrinsic-safety regulations can cause explosion and the resulting hazard
to people.

In hazardous areas, connections

to the control terminals must be

made using only instruments which
are permitted to be used in such areas.

mA

Ex-Milliammeter

TEST

To measure the current in the transmitter without
disconnecting the signalling circuit, connect
a milliammeter to control sockets , .

Hazardous area

Safe area

Aplisens KAP-03Ex Communicator

_

_

+

TEST

SIGNAL

+



RD

.

3

2

VWX

MNO

DEF

YZ#

5

6

PQR

*

+/

9

GHI

8

0

@%&

1

4

JKL

7

STU

ABC

RE

F2

PV

F4

F3

F4

PF

F1

Jumper

a Ex power supply
see p.5.

+

Ro

_



The transmitter is equipped in additional communication resistor

RD = 240 Ω.

During normal operation terminals

–> and are shorted.

RD resistor is used when you wish to communicate with the transmitter locally (from its terminals) and
Ro < 250

. Terminals

–> and must be opened.

Transmitter electrical installation should be realised with engineering standard requirements.

It is not allowed to repair or otherwise interfere with the transmitter’s electrical circuits in any
way. Damage and possible repair may be assessed only by the manufacturer or another
authorized party.

28V

– 13.5V** – (300Ω*

*

0,02A)

0,023A

Uzas.

– 13.5V**

0,023A

i
i

Delta Controls KAP-03Ex Communicator