Metrological parameters, Measurement ranges, List of current alarms – Delta Controls DPT-2000 User Manual

Page 15

background image

13 IOM-DPT-A: FEB 2014

The value of transmitter minimal supply voltage can be calculated from the following formula:

Umin = 12 + 0,023 x Ro [V] for transmitter operating without LCD display backlight
(or read from the drawing below)

Umin = 15 + 0,023 x Ro [V] for converter operating with LCD display backlight.
(or read from the drawing below)

Transmitters made in Ex version are delivered with display backlight switched off. The user can switch
the backlight on by himself.

0

250

500

750

1000

10

15

20

25

30

35

40

45

Ro[ ]

V

m

in

[V]

Umin = f(Ro) z podświetleniem

0

250

500

750

1000

10

15

20

25

30

35

40

45

Ro[ ]

V

m

in

[V]

Umin = f(Ro) bez podświetlenia

50

55

50

55

1250

1500

1750

1250

1500

1750

Supply voltage dependence on current loop resistance

Safe working area (grid) upper colour area.


Voltage for insulation testing

500 VAC or 750 VDC, see p.8.3.

Excess voltage protection

see p.8.3.

List of current alarms

Alarm Type

Value of Alarm Current

Alarm Type

Value of Alarm Current

NORMAL LOW

3,75 mA

CUSTOM (value of alarm

current is defined by user)

Value of alarm current in

interval

3,6 mA

23 mA

NORMAL HIGH

21,6 mA

NAMUR LOW

3,6 mA

LAST VALUE

(transmitter does not

update analog exit)

Alarm current value is equal

to the current value in the

time preceding the event

which giving an alarm.

NAMUR HIGH

21,0 mA

5.2. Metrological parameters.

Additional voltage damping

0...30s

Total error of transmitter (digital value)

± (0,05 + 0,05%·z + 0,001·|t|) °C for sensor Pt100

± (0,5 + 0,05%·z)°C for sensor K and t

375°C

± (0,5 + 0,05%·z + 0,002·(t-375))°C for sensor K and t

>375°C

Additional

analogue output error

± 0,04%·z

where:

|t| - modulus of measured temperature in °C

t - the value of measured temperature in °C

z - the range width of transmitter in °C

5.3. Measurement ranges.

Sensor type

Min. measuring range

Nominal range

Calibrated range

Pt 100

10 °C

- 200 ... 550 °C

0 ... 100 °C

Ni-Cr-Ni /K/ *

10 °C

- 40 ... 550 °C

0 ... 300 °C

*

Recommended for measurements with strong vibrations.

i

Ro[Ω]

Ro[Ω]

Vm

in

[

V]

Vm

in

[

V]

Umin = f(Ro) without display backlight

Umin = f(Ro) with display backlight