For successful communication with transmitter the resistance in measuring loop, behind connected
device to communication, should be higher than 250Ω. If necessary install the additional resistor in the
line. The communicator or modem connecting ways to the measuring loop are presented at diagrams.
During increasing of resistance in the measure loop at making the good transmission, is necessary to
make sure that the tension falls at sum resistances in the loop don't lower minimum tension at
transmitter terminals. (see p.5.1.).