beautypg.com

Calibration – Bray 6A Series Quick Start User Manual

Page 4

background image

Calibration

Step 1: Power on the unit with a 4 to 20 mA
signal.

Step 2: Press the button below the ‘ ‘
symbol for >5 seconds to enter into the
configuration mode.

Step 3: Once the configuration mode has been
initialized, parameter 1 is displayed on the
positioner window. Parameter 1 allows the
user to select the type of actuator being used
with the device.

Step 4: Using the ‘ ‘and ‘ ‘ buttons,
scroll through the available options until you
reach ‘turn’. This option is for quarter turn
actuators.