Alpha Technologies PME Series User Manual
Page 18
031-161-B0-006, Rev. F
18
2.0 Installation,
continued
2.1 Pole-mounting,
continued
2.1.2 Concrete or Steel Pole
Tools and Materials Required (customer supplied):
•
Stainless steel banding (or equivalent), rated to support loaded enclosure and
sized for pole diameter
• Assorted
sockets
Procedure:
1. Unpack the enclosure and galvanized brackets; turn the enclosure facedown on
a soft surface.
2. Slide a bracket up through the enclosure’s lower mounting bracket. The bracket’s
fl anges must face away from the enclosure. Secure the lower mounting bracket
using the 3/8" x 3/4" (9.5mm x 19mm) hex bolt included.
3. Position the upper mounting bracket on the pole and secure using banding.
4. Lift the enclosure onto the upper mounting bracket and pull downward to properly
seat it. Center the enclosure on the pole.
5. Secure the lower mounting bracket on the pole using banding. Spacing between
banding is as follows:
6. The enclosure is now ready for the utility connection, power module, and
batteries.
Enclosure
Distance (on center) (in/mm)
PWE-3 and PME
18"/457.2
PWE-4
15"/381
PWE-6
30"/762
PWE-8, PWE-9,
PWE-D36 (three straps)
15" (30" total)/
381 (762 total)