6 inverter battery dc sense interface connector, 5 ecm enclosure alarm interface connector – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual
Page 76

76
745-020-B0-003, Rev. C
Fig. 8-5, ECM Enclosure Alarm Interface Connector
8.6 Inverter Battery DC Sense Interface Connector
ECM - Inverter Battery DC Sense Interface Connector J8. The interface control is a 3-pin (1x3
row) Mini Mate-’N’-Lok style connector.
Fig. 8-6, Inverter Battery DC Sense Interface Connector
Pin
Description
Function
1
Water Intrusion Sensor
Contact OPEN (HIGH signal) denotes water
2
Water Intrusion common
Return signal path for sensor
3
Pad Shear Sensor
Contact CLOSED (LOW signal) denotes pad shear
4
Pad Shear Common
Return signal path for sensor
5
Low Fuel Pressure Sensor
Contact CLOSED (LOW signal) denotes low fuel
pressure (LP versions only)
6
Low Fuel Pressure Common
Return signal path for sensor
7
Gas Hazard Sensor Switch
Active OPEN signal denotes gas hazard (Logic HIGH)
8
Gas Hazard Power/Alarm
Return signal path for sensor (Common)
9
Gas Hazard Logic Power
Logic power for Logic PCB & sensor (+12VDC Fused)
10
Door Open Sensor
Contact CLOSED (LOW signal) denotes door is open
11
Door Open Common
Return signal path for sensor
12
No Connection
13
+12V Fused
LPG fuel monitor
14
Common
Return path for LPG fuel monitor
8.0 Interconnection,
continued
8.5 ECM Enclosure Alarm Interface Connector
The Alarm Interface Connector (J10) is connected to the Power PCBA. The interface control
is a 14-pin (2x7 row) Universal Mini Mate-’N’-Lok style male connector.
REAR
VIEW
WIRE
SIDE
J10
REAR
VIEW
Pin
Description
Function
1
DC Bus Sense (POS.)
Output inverter battery bus – positive connection, 48 and 98VDC buses
2
No Connection
3
DC Bus Sense ( NEG.)
Output inverter battery bus – positive connection, 48 and 96VDC buses
REAR
VIEW
REAR
VIEW
WIRE
SIDE
J8