2.0 Installation, continued

2.7 Enclosure Grounding

Site Service Grounding (Minimum Requirement)
Low-impedance earth protection from enclosure to earth potential (lightning/transient protection) is

provided by #6 bare copper wire connecting enclosure ground point and site grounding system. The site

grounding system, at a minimum, must be comprised of 2 ground rods 1/2" diameter x 8' in length driven

into the ground at least 6' apart.

Lightning Protection Ground Ring

1/2" X 8' copper ground rods, driven at least

two feet from pad

#6 bare copper wire ring, at least 30" below

grade, and terminated at each ground rod

#6 bare copper wire from ring to enclosure

ground point

1

2

3

Fig. 2-13, Pole Mount Lightning

Protection (Recommended Installation)

Burndy YGHP58C2W-3

or Equivalent

#6 Bare Copper Wire from

Enclosure Ground Point

1

1

1

2

3

1

Fig. 2-11, Lightning Protection Ground Ring

(Recommended Installation)

Burndy YGHP58C2W-2TN

or Equivalent

Terminate at Enclosure

Ground Point

Front of Pad

2' Minimum

Alpha Technologies recommends using the grounding method illustrated below. The grounding method for a

particular site is dependant upon soil type, available space, local codes, NEC (National Electric Code), and

other site-specific characteristics.

NOTE:

Fig. 2-12, 3/8" 2-Hole, 1" Ct, Enclosure

Ground Mount Location

ATTENTION:

It is the responsibility of the installer to meet the requirements of all applicable national and local codes. Alpha

Technologies assumes no responsibility or liability for failure of the installer to comply with the requirements of all

applicable local and national codes.