Xylem CHATTER Notification System configuration guide User Manual
Page 32

MANUAL
GB CHATTER NOTIFICATION CONFIGURATION 1303
32
Example:
DDMMYY
Key
Description
cnsCSVdateDelimiter
This key describes which character is used between the various elements in the
date when it is exported to the GE Proficy iFix version 5 Historian SCADA-system
The value is a single character, the value depends on the type of SCADA-system,
you will supply data to.
Example:
/
Key
Description
cnsCSVtimeFormat
This key describes how time is formatted in the file with comma-separated values,
delivered to the GE Proficy iFix version 5 Historian SCADA-system
The value is a string representing the time format:
Value
Description
HM
Exports the time as
the hour without a leading zero (0-23)
the minute without a leading zero (0-59).
HHMM
Exports the time as
the hour with a leading zero (00-23)
the minute with a leading zero (00-59).
+++
HMS
Exports the time as
the hour without a leading zero (0-23)
the minute without a leading zero (0-59)
the second without a leading zero (0-59).
HHMMSS
Exports the time as
the hour with a leading zero (00-23)
the minute with a leading zero (00-59)
the second with a leading zero (00-59).
Example:
HHMM
Key
Description
cnsCSVtimeDelimiter
This key describes which character is used between the various elements in the
time when it is exported to the GE Proficy iFix version 5 Historian SCADA-system
The value is a single character, the value depends on the type of SCADA-system,
you will supply data to.