Configuration of the scada plug-in, This chapter – Xylem CHATTER Notification System configuration guide User Manual
Page 29

MANUAL
GB CHATTER NOTIFICATION CONFIGURATION 1303
29
Configuration of the SCADA plug-in
Detailed configuration of SCADA plug-in
How SCADA plug-in is working is described in a configuration file. This file is a text file in XML format
If this configuration file is modified, the Chatter - Notification Service must be restarted
Filename and -location
C:\Program Files\MJK Automation\Chatter - Notification Service
cnsSCADAplugInGlobalConfig.xml
Description of the configuration file for SCADA plug-in
Key
Description
cnsVersion
This key contains the version number of this configuration file. The key is used by
Do not change the values in this key without
consulting MJK Automation ApS!
Example:
003
Key
Description
cnsSCADAsystemName
This key describes which type of SCADA-system, the SCADA plug-in will supply
data for.
The value is a string representing the name of the SCADA-system.
Value
Description
IGSS
The output from SCADA plug-in wil be in a format
acceptable to IGSS32 release 8 or IGSS32 release 9
IFIX
The output from SCADA plug-in wil be in a format
acceptable to GE Proficy iFix version 5 Historian
BV2000
The output from SCADA plug-in wil be in a format
acceptable to BV Electronics System 2000
Example:
IGSS
Key
Description
cnsCSVifixTagFile
This key describes the name of and the path to a file with comma-separated
values with tag-names from the SCADA plug-in exported to the GE Proficy iFix
version 5 Historian SCADA-system.