First element, Second element, Third element – Xylem CHATTER Notification System configuration guide User Manual
Page 27: Fourth element, Fifth element

MANUAL
GB CHATTER NOTIFICATION CONFIGURATION 1303
27
Terminating NEengine
Notification Engine: Stopping service
Key
Description
cnsTriggers
This key contains five values, separated by a semicolon
An identification number for the plug-in treating data from this rule.
data to this rule.
data to this rule.
A digit pointing at a supplementary
A letter describing the type of data, either a measurement or an alarm,
supplying data to this rule.
First element
The first element is a digit, the identification number for the plug-in treating data
from this rule:
#1
Description
0;
Data will not be treated by any plug-in
1;
Data will be treated by the SCADA plug-in
2;
Data will be treated by the STORMFLOW plug-in
Second element
Data Logger supplying data to this rule.:
#2
Description
D;
a digital input
A;
Data must come from an analog input
C;
Data must come from a counter on a digital input.
M;
Data must come from a Modbus input
I;
Data must come from an internal measurement
Third element
Logger supplying data to this rule.
#3
Description
1;
Data must come from X-input number 1
2;
Data must come from X-input number 2
3;
Data must come from X-input number 3
4;
Data must come from X-input number 4
Fourth element
The fourth element is a digit pointing at a supplementary
Fifth element
The fifth element is a letter describing the source of data, either an alarm or a
measurement:
17