beautypg.com

OSRAM DALI CON 1…10 LI User Manual

Page 2

background image

Page 2/4

Operating instructions for DALI CON 1 – 10V LI

Operating instructions for DALI CON 1 – 10V LI

Page 3/4

DALI interface

Interface in accordance with the DALI standard. Current input <2mA DC. Electrical isolation via opto-coupler
from mains and output: basic insulation (no safety extra-low voltage).
The converter does not have an integrated power supply for the DALI interface. The power supply for the DALI
interface has to be part of the DALI controller.

Output (combined interface) 1-10V/0-10V

Interface for controlling 1-10V units (max. -100 mA current sink e.g. for ECG, electronic transformers, etc.)
and/or 0-10V units (max. +5 mA active e.g. for power dimmers, etc.). Electrical isolation from the mains and
DALI: basic insulation (no safety extra-low voltage).

Characteristic switch

Switching option for the characteristic for the control voltage at the output. Linear from 0 – 10V, usually for power
dimmers. Logarithmic from 1 – 10V, usually for ECG and electronic transformers.

Load contact

Internal relay (make contact) not floating. The load contact is connected internally with L. Suitable for direct
on/off switching of small systems. Check the contact load rating. Add an external relay or contactor for larger
systems. On/off switching as function switching.

Switch input

Switch input for operating in 1-button mode. Switching takes place to L (make contact/230Vac). Internal opto-
coupler to N (mains potential).
Electrical isolation from the output and DALI: basic insulation (no safety extra-low voltage).

Safety and installation instructions

Power to the units must be switched off before any work is undertaken.

The units should be installed and tested only by a qualified electrician.

Wire the terminals as shown in the wiring diagram. Follow the wiring diagrams and any printed
instructions on the unit.

The relevant safety and accident prevention regulations must be observed.

The relevant installation instructions must be observed.

The unit must not be opened or operated without its casing.

Dimensional drawing:

















Usage

of DALI and 1-button operation at the same time is not allowed!
The converter may be damaged or destroyed if wired incorrect!