Wiring and configuration of the ecg – OSRAM OPTOTRONIC Constant current LED power supplies with 3DIM User Manual
Page 10
10
WIRING AND CONFIGURATION OF THE ECG
4.1.2. Control line – cable requirements
The maximum total cable length of a DALI
®
control line is
300 m. When selecting a cable, it must be ensured that the
voltage drop on the control line does not exceed 2 V at
250 mA.
The following table can be used as a quick reference guide
for selecting the correct cable cross-section.
Note: For reasons of clarity, it is recommended to use the
black and gray wire of the cable for the DALI
®
connection
(see fi gure 12).
Table 2: Recommended cable cross-sections
Cable length
up to 100 m
100 to 150 m
150 to 300 m
Cable cross-section
0.5 mm
2
0.75 mm
2
1.5 mm
2
Figure 13: Connection of multiple 3DIM ECGs via DALI
®
control line.
Figure 12: Individual wires of a DALI
®
control line.
e.g. NYM 5x…
Neutral conductor
DALI
®
(DA)
DALI
®
(DA)
Protective
earth
Phase
Luminaire 1
Depending on
the ECG type
3DIM ECG
LED out
L
L
L
N
N
N
SD
SD
SD
DA
DA
DA
DA
DA
DA
LED out
LED out
3DIM ECG
3DIM ECG
Depending on
the ECG type
Depending on
the ECG type
Light
load
Light
load
Light
load
Luminaire 2
Luminaire 3
DALI
®
bus/
DALI
®
controller
L
N
DA
PE
DA
PE N L