Trouble shooting – PowerWalker Battery Pack for VFI 1000RT LCD User Manual
Page 34
30
EN
8. Trouble Shooting
If the UPS system does not operate correctly, check the operating status on the LCD
display.
Warning
String Fault
String
Site fail
SITE
Inverter short
SHOR
Fan fail
FANF
Overload fault
OVLD
Battery over voltage (over charged)
HIGH
Inverter soft start fail
ISFT
Battery low
bLOW
Bus soft start fail
bSFT
Charge fail
CHGF
Over temperature fault
OVTP
Inverter temperature high
TEPH
Inverter voltage low
INVL
Ambient temperature high
AMbH
Inverter voltage high
INVH
Battery open
bOPN
Bus voltage over
bUSH
Overload
OVLD
Bus voltage Low
bUSL
EPO
EPO
Bus voltage unbalance
bUSE
Battery fault
bATF
Bus short
bUSS
NTC open
NTCO
If the UPS system does not operate correctly, please attempt to solve the problem
using the table below.
Problem
Pzle cause
Remedy
No indication, no
warning tone even
though system is
connected to mains
power supply
No input voltage
Check building wiring socket outlet
and input cable.
Display Mode
string ”STbY” in LCD,
even though the power
supply is available
Inverter not switched on
Press On-Switch “I”.
Display Mode
string ”bATT” in LCD,
and audible alarm
sounding every 1 beep
in every 4 seconds
Mains power supply has
failed, or Input power
and/or frequency are out
of tolerance
Switching to battery mode
automatically.
Check input power source and inform
dealer if necessary.
Emergency supply
period shorter than
nominal value
Batteries not fully charged
/ batteries defect
Charge the batteries for at least
5 - 8 hours and then check capacity.
If the problem still persists, consult
your dealer.
Fan fail
Fan abnormal
Check if the fan is running
Battery over voltage
Battery is over charged
Stop charging to battery
automatically, and after the battery
voltage is normal and the mains is
normal, charge automatically again.