8. Trouble Shooting

If the UPS system does not operate correctly, check the operating status on the LCD

display.

Warning

String Fault

String

Site fail

SITE

Inverter short

SHOR

Fan fail

FANF

Overload fault

OVLD

Battery over voltage (over charged)

HIGH

Inverter soft start fail

ISFT

Battery low

bLOW

Bus soft start fail

bSFT

Charge fail

CHGF

Over temperature fault

OVTP

Inverter temperature high

TEPH

Inverter voltage low

INVL

Ambient temperature high

AMbH

Inverter voltage high

INVH

Battery open

bOPN

Bus voltage over

bUSH

Overload

OVLD

Bus voltage Low

bUSL

EPO

EPO

Bus voltage unbalance

bUSE

Battery fault

bATF

Bus short

bUSS

NTC open

NTCO

If the UPS system does not operate correctly, please attempt to solve the problem

using the table below.

Problem

Pzle cause

Remedy

No indication, no
warning tone even
though system is
connected to mains
power supply

No input voltage

Check building wiring socket outlet
and input cable.

Display Mode
string ”STbY” in LCD,
even though the power
supply is available

Inverter not switched on

Press On-Switch “I”.

Display Mode
string ”bATT” in LCD,
and audible alarm
sounding every 1 beep
in every 4 seconds

Mains power supply has
failed, or Input power
and/or frequency are out
of tolerance

Switching to battery mode
automatically.

Check input power source and inform
dealer if necessary.

Emergency supply
period shorter than
nominal value

Batteries not fully charged
/ batteries defect

Charge the batteries for at least

5 - 8 hours and then check capacity.
If the problem still persists, consult
your dealer.

Fan fail

Fan abnormal

Check if the fan is running

Battery over voltage

Battery is over charged

Stop charging to battery
automatically, and after the battery
voltage is normal and the mains is
normal, charge automatically again.