Page 27

background image

23

EN

(3) The battery connection procedure is very important. Any

incompliance may result in the risk of electric shock. Therefore, the
following steps must be strictly complied with.

(4) Make sure the mains input is cut off, if there is a battery breaker then

turn it off first.

(5) Remove front panel, connect the battery via Anderson PP45

connectors. Prepare the battery cable which should be able to carry
the current of >50A for all models, the cross section area should be
great than 4 mm

2

for all model. And battery wire color is

recommended as following:

GND

Red wire

Green/Yellow wire

Black wire

(6) The red wire is connected to the "+" terminal of the battery. The black

wire is connected to the "-" terminal of the battery. (Note: the
green/yellow wire is grounded for protection purpose.)

(7) Make sure the wires are fasten, install the terminal block cover on the

rear panel of the UPS.

(8) Connect the UPS to the load. Then, turn on the mains switch or

connect the power cord of the UPS to utility power supply, the battery
would start to be charged.










Caution:

A DC breaker must be connected between the UPS and external battery.

Caution:

The output sockets of the UPS system may still be electrically live even if the
power supply system has been disconnected or the Bypass switch is on
“OFF” position.