Use No. 12 AWG (for 3KS input wire), 90

°

C copper wire and 4.4 lb-in

Torque force when connecting to terminal block.

Use No. 10AWG (for all models battery wire), 90

°

C copper wire and

Anderson PP45 connectors for user’s external battery cabinet.

1.3 Maintenance, servicing and faults

The UPS operates with hazardous voltages. Repairs may be carried out

only by qualified maintenance personnel.

Caution - risk of electric shock. Even after the unit is disconnected from

the mains power supply (building wiring socket), components inside the

UPS are still connected to the battery which are potentially dangerous.

Before carrying out any kind of service and/or maintenance, disconnect

the batteries. Verify that no current is present and no hazardous voltage

exists in the capacitor or BUS capacitor terminals.

Batteries must be replaced only by qualified personnel.

Caution - risk of electric shock. The battery circuit is not isolated from the

input voltage. Hazardous voltages may occur between the battery

terminals and the ground. Verify that no voltage is present before

servicing!

Batteries have a high short-circuit current and pose a risk of shock. Take

all precautionary measures specified below and any other measures

necessary when working with batteries:

remove all jewellery, wristwatches, rings and other metal objects

use only tools with insulated grips and handles.

When changing batteries, replace with the same quantity and the same

type of batteries.

Do not attempt to dispose of batteries by burning them. It could cause

explosion.

Do not open or destroy batteries. Effluent electrolyte can cause injury to

the skin and eyes. It may be toxic.

Please replace the fuse only by a fuse of the same type and of the same

amperage in order to avoid fire hazards.

Do not dismantle the UPS, except the qualified maintenance personnel.