beautypg.com

B&B Electronics GW-7433D - Quick Start Guide User Manual

Page 8

background image

Æ The column is Modbus TCP DO address, the row range is 0 ~63.

Æ The row is CANopen slave device’s data byte address mapping to Modbus

TCP address.

3

2

Æ The row is CANopen slave device’s data byte address mapping to Modbus

TCP address.

4

Æ Close the “ShowMapping” window.

5

The “DI Mapping,” ”AI Mapping” and “AO Mapping” of mapping type the

same as the “DO Mapping” of mapping type. In these tabs, the PDO and SDO

arrayal of bytes are form PDO bytes to SDO bytes.

When user over view the “ShowMapping” window finish, Plase close the

“ShowMapping” window, when user close it then the GW-7433D Utility will

display the “MappingModules” window, then user have to close the

“MappingModules” window, the GW-7433D Utility will display the “GW-7433D

Utility ver(1.0.0)” window and click the “Disconnect with GW-7433D” button to

close the window to finish the GW-7433D Utility setting. As follow figure.

Close the GW-7433D Utility setting

GW-7433D MODBUS TCP/CANopen Gateway Quick Start User Guide (Version 1.0, July/2008) 8