B&B Electronics ZXT9-IO-222R2 - Quick Start Guide User Manual
Page 6

pn 8590R1-ZXTx-IO-x-2011QSG –Peer-to-Peer Mode
U
U
L
L
C
C
l
l
a
a
s
s
s
s
1
1
D
D
i
i
v
v
2
2
R
R
e
e
q
q
u
u
i
i
r
r
e
e
m
m
e
e
n
n
t
t
s
s
Operating Voltage – 10 to 30 VDC
WARNING: SUITABLE FOR USE IN CLASS I, DIVISION 
2, GROUPS A, B, C AND D HAZARDOUS LOCATIONS, 
OR NONHAZARDOUS LOCATIONS ONLY. 
WARNING - EXPLOSION HAZARD - SUBSTITUTION 
OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR 
CLASS I, DIVISION 2. 
WARNING – EXPLOSION HAZARD – WHEN IN 
HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE 
REPLACING ANTENNA. 
Intended use of equipment – please see the B&B 
Electronics Data Sheets and Quick Start Guides for each 
Zlinx Xtreme product for explanations of the intended use of 
this equipment. 
Wiring Terminals – Use Copper Wire Only, one conductor 
per terminal 
 
Wire Range 30 – 12 AWG 
 
Maximum Surrounding Ambient Air Temperature - 74°C
UL Class I, Division 2 wiring methods. The Zlinx Xtreme 
enclosure is provided with two conduit knockouts that serve 
as wiring provisions for Class I, Division 2 wiring methods 
per the National Electrical Code (NEC). 
The following instructions include procedures to be followed 
in order to ensure UL "separation between circuits" as 
defined in the NEC. 
The low-voltage (LV) wiring – DC power, analog & digital 
signals – must be separated from the high voltage (HV) 
wiring for the relay contacts. In all cases HV wiring must be 
rated minimum 250V. 
 
 
 
 
Separation between circuits can be accomplished by using one 
of the three following methods: 
a. Use one conduit knockout to route LV wiring and the
second conduit knockout to route the HV wiring, OR 
see methods 2 and 3 below. 
The remaining two methods use one conduit 
knockout for all wiring. In this case a UL Recognized 
(UL type QCRV2) conduit plug must be used per the 
NEC to plug the second conduit knockout. 
b. Enclose LV wiring in a 250V rated insulated sheath
to separate it from the HV wiring, OR
c. Use 250vac rated wires for both LV and HV wiring.
Temperature rating of field installed conductors - Field 
conductors shall be rated 60C/75C minimum (either are 
acceptable) and sized accordingly. 
When conduit openings are not being used, a UL 
Recognized plug (type QCRV2) shall be used. 
The following is UL-required information regarding the 
Sealed Relay Devices: 
WARNING – Exposure to some chemicals may degrade 
the sealing properties of materials used in the Sealed 
Relay Device. 
RECOMMENDATION – It is recommended to inspect the 
sealed relay device periodically and to check for any 
degradation of the materials and to replace the 
component product, not the sealed device, if any 
degradation is found. 
Sealed Relay Device Information: 
 
Sealed Device: Relay Models G6RL-14-ASI-DC5, G6RL-
14-ASI-DC6, G6RL-14-SR-ASI-DC5 or G6RL-14-SR-ASI-
DC6 manufactured by Omron Corp. 
 
 
Manufacturer Type
Relay Case and 
Base 
Mitsubishi 
Engineering 
Plastics 
Corp. 
5010GN6-30M8AM
Sealant
TB2225G
Three Bond 
Ltd. 
11
