Section 3 - Operation

Liquid-cooled Generators

¥ Unless otherwise specifically permitted in the NEC, the overcurrent protection for conductor types marked with an ¥ shall

not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12
and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and
number of conductors have been applied.

SIZE

TEMPERATURE RATING OF CONDUCTOR

SIZE

60° C

75° C

90° C

60° C

75° C

90° C

(140° F)

(167° F)

(194° F)

(140° F)

(167° F)

(194° F)

TYPES

TYPES

TYPES

TYPES

TYPES

TYPES

TW¥, UF¥

FEPW¥

TA, TBS, SA

TW¥

RH¥, RHW¥

TA, TBS

RH¥, RHW¥

SIS, FEP¥

UF¥

THHW¥

SA, SIS,

AWG

THHW¥

FEPB¥

THW¥

THHN¥

AWG

kcmil

THW¥

RHH¥, RHW2

THWN¥

THHW¥

THWN¥

THHN¥, THHW¥

XHHW¥

THW2, THWN2

XHHW¥

THW2,

THWN2

USE¥

RHH¥,

RHW2

USE¥, ZW¥

USE2, XHH

USE2

XHHW¥

XHH,

XHHW

XHHW2, ZW2

XHHW2, ZW2

COPPER

ALUMINUM OR COPPER CLAD ALUMINUM

18

14

16

18

14

20¥

20¥

25¥

12

25¥

25¥

30¥

20¥

20¥

25¥

12

10

30

35¥

40¥

25

30¥

35¥

10

8

40

50

55

30

40

45

8

6

55

65

75

40

50

60

6

4

70

85

95

55

65

75

4

3

85

100

110

65

75

85

3

2

95

115

130

75

90

100

2

1

110

160

150

85

100

115

1

1/0

125

150

170

100

120

135

1/0

2/0

145

175

195

115

135

150

2/0

3/0

165

200

225

130

155

175

3/0

4/0

195

230

260

150

180

205

4/0

250

215

255

290

170

205

230

250

300

24

285

320

190

230

255

300

350

260

310

350

210

250

280

350

400

280

335

380

225

270

305

400

500

320

380

430

260

310

350

500

600

355

42

475

285

340

385

600

700

385

460

520

310

375

420

700

750

400

475

535

320

385

435

750

800

410

490

555

330

395

450

800

900

435

520

585

355

425

480

900

1000

455

545

615

375

445

500

1000

1250

495

590

665

405

485

545

1250

1500

520

625

705

435

520

585

1500

1750

545

650

735

455

545

615

1750

2000

560

665

750

470

560

630

2000

‹

TABLE 3 — ALLOWABLE AMPACITIES OF INSULATED CONDUCTORS RATED 0-2000 VOLTS, 60° TO 90° C

(140° TO 194° F). NOT MORE THAN THREE CONDUCTORS IN RACEWAY OR CABLE OR EARTH
(DIRECTLY BURIED), BASED ON AMBIENT TEMPERATURE OF 30° C (86° F) (REFERENCE NEC
TABLE 310-16)