2 Amp and 10 Amp
Battery Chargers

Specifications

2 Amp

10 Amp

Nominal Input

120 VAC

120 VAC

Operating AC Line Voltage Range

108 to 132 Volts AC

108 to 132 Volts AC

Input AC Line Frequency

50/60 Hz

50/60 Hz

Battery Fuse

5 Amps

15 Amps

Nominal Charge Rate

2 Amps

10 Amps

Equalize Voltage

13.8 Volts

Float Voltage

13.8/27.6

13.0/26.0

Current @ Equalize to Float Transition

5 Amps

Battery Under-voltage shutdown

11/22 Volts

11/22 Volts

LED Indicators
AC Line Voltage

Green LED On

Green LED On

Battery Connected and Charging

Yellow LED On

Yellow LED On

1 > 0.5 Amp

1 > 2 Amp

Battery Current Drain

30 milliamp

30 milliamp

AC Line Connection

Terminal Block

Terminal Block

Battery Connection

Internal to Control Panel

Internal to Control Panel

Control Connection

AC Power Fail Relay

Form C 2 Amp Rating

UL Listed

Yes

Yes

NFPA110 Compliant

No

Yes

The Olympian 2 & 10 Amp 12 and
24 Volt charger is designed to work
with the H control panel is mounted
within the H100 Enclosure. It
provides the ultimate in automatic
battery voltage maintenance.

The 2 amp is self regulating and
produces instantaneous output
current adjustments to keep the
battery charged to an optimum level.
Battery voltage is read on the H100
control panel readout The 10 amp
has automatic float and equalizer
control. It precisely monitors the
battery’s voltage and automatically
activates the correct charging mode.

The charge rate is limited and
controlled to efficiently and safely
maintain ideal battery levels under
varying conditions.

The equalizer system uses a control
circuit to limit charging current to 10
amps. When battery voltage drops
beyond a pre-set level, charging
current increases to 5 amps and
then to the 10 amp charge rate if
needed. When the battery reaches
maximum charge the charger
switches to equalize mode. At
equalize, just enough current is
supplied to maintain the battery at
or above 13/26 volts. Battery voltage
and Charging current are read at the
digital display on the H100 panel.

Battery Charger shown from inside of Control Panel Enclosure.
Connections are made via an attached harness.

Information contained in this publication may be considered confidential.

Discretion is recommended when distributing.

Materials and specifications are subject to change without notice.

CAT, CATERPILLAR, OLYMPIAN, their respective logos and ''Caterpillar Yellow'', as well as corporate and product

identity used herein, are trademarks of Caterpillar and may not be used without permission.

www.CAT-ElectricPower.com

© 2009 Caterpillar
All rights reserved.

Printed in U.S.A.

This manual is related to the following products: