Milton CAT G100LG4-2 100kW_125kVA Open Sound Data User Manual
Sound test results, Genset: enclosure
![background image](/manuals/268265/1/background.png)
Genset:
Enclosure:
Right
Left
Sound Test Results
G100LG 9.0L
Non-Enclosed Unit (Open Set)
Front
Back
Measured Sound Levels - 60 Hz
RADIATOR END
GENERATOR END
Pos 1
Pos 2
Pos 3
Pos 4
OLYMPIAN POWER SYSTEMS, INC.
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0196710SSD 08/12
Notes:
1. All positions 23 ft (7M) from side faces of generator set.
2. Generator operating at full load.
3. Test conducted on a 100 foot diameter asphault surface.
4. Non-enclosed sets do not include exhaust sound during testing.
79.7
86.9
85.0
83.7
72
74
76
78
80
82
84
86
88
90
92
94
96
1
2
3
4
dB
(A
)
@ 7 M
e
ter
s
Position Number
Measured Sound Levels - 60 Hz
Actual
Average
Avg. 83.8 dBA