Milton CAT G275LG 275kW_344kVA Level 1 Attenuated Enclosure Sound Data User Manual
Sound test results, Genset: enclosure
Genset:
Enclosure:
Back
Right
Left
Front
Notes:
1. All positions 23 ft (7M) from side faces of generator set.
2. Generator operating at full load.
3. Test conducted on a 100 foot diameter asphault surface.
Sound Test Results
G275LG 13.3L
Sound Attenuated Enclosure
Measured Sound Levels - 60 Hz
77.6
81.8
86.3
81.0
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
1
2
3
4
Position Number
dB
(A
) @ 7 Meter
s
Actual
Average
Ave. 81.7 dBA
RADIATOR END
GENERATOR END
Pos 1
Pos 2
Pos 3
Pos 4
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0604140SSD 06/07