Milton CAT C27 Sub-Base Fuel Tank Base User Manual
C27 sub-base fuel tank base, Features description, Options

A T T A C H M E N T S
LEHE7416-00
FEATURES
DESCRIPTION
C27 SUB-BASE
FUEL TANK BASE
Griffin
Diesel Generator Set
750-900 kVA 50 Hz
650-800 kW 60 Hz
●
UL 142 listed
●
Designed and built to comply with NFPA 30,
37, 110
●
Tank design provides capacity for thermal
expansion of fuel
●
Direct reading fuel level gauge
●
Fuel supply dip tube is positioned so as not
to pick up fuel sediment
●
Fuel return and supply dip tubes are separated
by an internal baffle to prevent recirculation
of heated return fuel
●
Fuel fill – 101.6 mm (4 in), lockable flip top cap
●
Primary tank level detection switch in
containment basin
●
Primary and secondary tanks are leak tested
at 20.7 kPa (3 psi) minimum
●
Welded steel containment basin (minimum
of 110% of primary tank capacity)
●
Interior tank surfaces coated with a solvent-
based thin-film rust preventative
●
Heavy gauge steel gussets suitable for lifting
package
●
Gloss black polyester alkyd acrylic enamel
exterior paint over epoxy based primer
●
Primary tanks are equipped with customer
connections for remote fuel transfer, return
and vent
●
Dual wall, secondary containment
●
Heavy construction 6 mm (0.24 in) steel plate
side channels and 4 mm (0.16 in) sheet steel
tank design
●
Rear and right side stub-up access
●
Emergency vents on primary and secondary
tanks are sized in accordance with NFPA 30
●
Leak detection switch
●
Compatible with enclosures (weather
protective and sound attenuated)
●
The sub-base fuel tank mounts below the
generator set wide base
OPTIONS
●
Manual fuel transfer pump
●
Low fuel level switch (alarm and shutdown)