beautypg.com

Milton CAT G150LG4 150kW_188kVA Level 2 Attenuated Enclosure Sound Data User Manual

Sound test results, Genset: enclosure

background image

Genset:

Enclosure:

Right

Left

Sound Test Results

G150LG 12.9L

Level 2 Acoustic Enclosure

Front

Back

Measured Sound Levels - 60 Hz

RADIATOR END

GENERATOR END

Pos 1

Pos 2

Pos 3

Pos 4

OLYMPIAN POWER SYSTEMS

DATA SUBJECT TO CHANGE WITHOUT NOTICE

0195970SSD 05/12

Notes:

1. All positions 23 ft (7M) from side faces of generator set.
2. Generator operating at full load.
3. Test conducted on a 100 foot diameter asphault surface.
4. Non-enclosed sets do not include exhaust sound during testing.

71.0

72.0

74.0

72.0

64

66

68

70

72

74

76

78

80

82

1

2

3

4

dB

(A

)

@ 7 M

e

ter

s

Position Number

Measured Sound Levels - 60 Hz

Actual

Average

Avg. 72.3 dBA

OLYMPIAN POWER SYSTEMS

DATA SUBJECT TO CHANGE WITHOUT NOTICE

0195970SSD 05/12