Milton CAT G200LG4 200kW_250kVA 21 Light Remote Annunciator User Manual
21 light remote annunciator
The remote Annunciator Panel provides remote monitoring
and annunciation of up to 18 generator parameters using
LED’s located on the annunciator keypad. It also provides
two system level warnings which are System Ready and
Communications OK.
The Relay panel has up to 8 selectable functions on form
A relays, and multiple relay panels can be connected for
all 18 generator parameters.
The specific faults can be selected using either the DIP
switches located on the annunciator circuit board or through
a computer via the RS232 connection on the circuit board.
All relays are energized on power up and open during a
fault condition.
Communication is via a RS485 serial data link and power is
supplied by the generator battery (+12V dc or +24 V dc)
21 Light Remote Annunciator
Description:
Environmental Specifications:
Operating Temperature ............................................................................................................................-25 º C to 60 º C
Humidity .................................................................................................................................0 to 95% Non Condensing
Power Supply .................................................................................................................................... +12 or +24 Volts DC
Power Usage .............................................................................................................................................. 6 watts typical
Power Supply ........................................................................................................................................Generator Battery
Communication Line ........................................................................... RS485 fully isolated twisted pair cable with shield
Maximum Cable Length ......................................................................................................................................4000 feet
Relay Output .............................. One NO contact ( Engergized when annunciator is powered and no faults are present
Relay Contact Rating ............................................................................................................................... 30 VDC, 1 amp
Model 0054650 Remote Annunciator Panel without Relays
Model 0054660 Remote Relay Panel without LED’s and Keypad ( Relays Only)
Model 0054640 Remote Annunciator Panel with 8 Relays
Model 0056370 Flush Mount Enclosure w/o Annunciator