beautypg.com

3 mounting, 1 basic standby electric system, 2 standby circuit isolation method – Milton CAT G200LG4 200kW_250kVA LG Installation Guide User Manual

Page 14: 3 total circuit isolation method, Connection diagrams

background image

12

2.3 MOUNTING

Mounting dimensions for the transfer switch enclo-
sure can be found in the transfer switch owner’s
manual. Enclosures are typically wall-mounted.

Handle transfer switches carefully when install-

ing. Do not drop the switch. Protect the switch
against impact at all times, and against construc-
tion grit and metal chips. Never install a transfer
switch that has been damaged.

Install the transfer switch as close as possible to the
electrical loads that are to be connected to it. Mount
the switch vertically to a rigid supporting structure.
To prevent switch distortion, level all mounting
points. If necessary, use washers behind mounting
holes to level the unit. Never install the switch where
water or any corrosive substance might drip into the
enclosure.

3.1

BASIC STANDBY ELECTRIC
SYSTEM

Figure 3.1 shows a schematic diagram of a basic
standby electric system. Both the UTILITY power
supply and the STANDBY (GENERATOR) output are
connected to an approved transfer switch. The trans-
fer switch is required by electrical code and serves
the following functions:

• Allows the LOAD circuits to be connected to only

one power supply at a time.

• Prevents electrical backfeed between the generator

and the UTILITY power circuits.

Figure 3.1 – Basic Standby Electric System

Notice that both the STANDBY and the UTILITY
power supplies to the transfer switch are protected
against overload by a main line circuit breaker.

3.2

STANDBY CIRCUIT ISOLATION
METHOD

This prevents overloading the generator by keeping
electrical loads below the wattage/amperage capac-
ity of the generator. If the generator is powering only
designated loads, within the wattage/amperage capac-
ity, during utility power outages, consider using the
emergency circuit isolation method.

Designated electrical loads are grouped together and
wired into a separate “Standby Distribution Panel.”
Load circuits powered by that panel are within the
wattage/amperage capacity of the generator set. When
this method is used, it is difficult to overload the gen-
erator. The transfer switch must meet the following
requirements:

• It must have an ampere rating equal to the total

amperage rating of the standby distribution panel
circuit.

• Have it installed between the building’s main distri-

bution panel and the standby distribution panel.

3.3

TOTAL CIRCUIT ISOLATION
METHOD

When a generator capable of powering all electrical
loads in the circuit is to be installed, use the “Total
Circuit Isolation Method.” It is possible for the gen-
erator to be overloaded when this isolation method is
employed. The following apply to the transfer switch
in this type of system.

• Ampere rating of the transfer switch must equal

the ampere rating of the normal incoming utility
service.

• The transfer switch is installed between the util-

ity service entrance and the building distribution
panel.

3.4. CONNECTION

DIAGRAMS

All wiring in the standby electric power system must
be in strict compliance with applicable codes, stan-
dards and regulations. Such wiring must be properly
supported, routed, and connected. In addition, wir-
ing must be properly sized to carry the maximum
load current to which is will be subjected.

The connections between the generator and transfer
switch will vary depending on the equipment ordered.
In each case there are two types of interconnections,
load wiring and control wiring.

NOTE:

Control wiring must always be run in a separate
conduit from the load wiring.

Section 3 - Operation

Liquid-cooled Generators

This manual is related to the following products: