Altronix AL600ULACMCBR Installation Instructions User Manual
Page 9
ACMCBseries
- 9 -
AL1024ULACMCB Battery Size Calculation Worksheet.
A. AL1024ULACMCB internal current consumption
(standby)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .35 A
B. Load current consumption
(standby)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A
C. Standby time required (hours)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ H
D. Battery capacity required for standby
(A+B)*C
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
E. AL1024ULACMCB internal power consumption
(Alarm)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .35 A
F.
Load current consumption
(Alarm)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A
G. Alarm duration (Hours, example:15 Min=.25 Hour)
(Alarm)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ H
H. Battery capacity required for Alarm
(E+F)*G
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
I.
Total calculated battery capacity
D+H
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
J.
Battery capacity required
I*1.8 (safety factor)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
Note:
AL1024ULACMCB power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceed 36AH. You have to reduce either standby current consumption or standby time in
order to comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size.