- 3 -
• Battery fail and battery presence supervision (form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
Enclosure dimensions: 15.5"H x 12"W x 4.5"D
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 10).
Secure enclosure to earth ground. It is recommended to first review the following tables to facilitate installation:
Output Voltage and Stand-by Specifications Charts
(pg. 3)
Typical Application Diagram
(pg. 5)
LED Diagnostics
(pg. 6)
Terminal Identification Tables
(pg. 7)
Hook-up Diagrams
(pg. 8)
2. Set output voltage:
AL400ULACMCB and AL600ULACMCB set desired DC output voltage by setting
switch SW1 to the appropriate position on the power supply board.
AL1012ULACMCB is 12VDC and AL1024ULACMCB is 24VDC
(Output Voltage and Stand-by Specification Charts below).
3. Measure voltage before connecting devices. This helps avoid potential damage.
Output Voltage and Stand-by Specification Charts:
AL400ULACMCB
Voltage
Switch
Stand-by
4 hr. Stand-by / 5 mins. Alarm
24 hr. Stand-by / 5 mins. Alarm
Position
Battery
12VDC
SW1 - Closed
40 AH
3.5 amp / 3.5 amp
.5 amp / 3.5 amp
24VDC
SW1 - Open
40 AH
2.75 amp / 2.75 amp
.75 amp / 2.75 amp
AL600ULACMCB
Voltage
Switch
Stand-by
4 hr. Stand-by / 5 mins. Alarm
24 hr. Stand-by / 5 mins. Alarm
Position
Battery
12VDC
SW1 - Closed
40 AH
5.5 amp / 5.5 amp
.5 amp / 5.5 amp
24VDC
SW1 - Open
40 AH
5.75 amp / 5.75 amp
.75 amp / 5.75 amp
AL1012ULACMCB
Voltage
Switch
Stand-by
4 hr. Stand-by / 5 mins. Alarm
24 hr. Stand-by / 5 mins. Alarm
Position
Battery
12VDC
N/A
40 AH
9.5 amp / 9.5 amp
.5 amp / 9.5 amp
AL1024ULACMCB - (refer to AL1024ULACMCB Battery Size Calculation Worksheet, pg. 9)
Voltage
Stand-by
15 mins. Stand-by /
4 hr. Stand-by /
24 hr. Stand-by /
60 hr. Stand-by /
Battery
5 mins. Alarm
5 mins. Alarm
5 mins. Alarm
5 mins. Alarm
24VDC
12 AH
7.7 amp / 9.7 amp
1.2 amp / 9.7 amp
-------------------------
-------------------------
Voltage
Stand-by
15 mins. Stand-by /
4 hr. Stand-by /
24 hr. Stand-by /
60 hr. Stand-by /
Battery
5 mins. Alarm
5 mins. Alarm
5 mins. Alarm
& 5 mins. Alarm
24VDC
65 AH
-------------------------
7.7 amp / 9.7 amp
1.2 amp / 9.7 amp
200mA / 9.7 amp