Altronix AL600ULACMCBR Installation Instructions User Manual
Page 7
ACMCBseries
- 7 -
Terminal Identification Tables:
Power Supply Board
Terminal
Function/Description
Legend
L, G, N
Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.
- DC +
AL400ULACMCB - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power limited).
AL600ULACMCB - 12VDC/24VDC @ 6 amp to ACM8CB board (power limited).
AL1012ULACMCB - 12VDC @ 10 amp to ACM8CB board (power limited).
AL1024ULACMCB - 24VDC @ 10 amp to ACM8CB board (power limited).
AC FAIL
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay
NC, C, NO
normally energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to
6 hrs., cut “AC delay” jumper and reset power to unit.
BAT FAIL
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally
NC, C, NO
energized when DC power is present. Contact rating 1 amp @ 28VDC.
A removed battery is reported within 5 minutes. Battery reconnection is reported
within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACMCB),
24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACMCB).
- BAT +
Stand-by battery connections. AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply
Board) maximum charge current is .7 amp. AL1024ULXB (Power Supply Board)
maximum charge current is 3.6 amp.
ACM8CB Access Power Controller
Terminal
Function/Description
Legend
- Power +
12VDC or 24VDC input from power supply board.
- Control +
These terminals can be connected to a separate power limited, UL listed power supply to
provide isolated operating power for the ACM8 (jumpers J1and J2 Must be removed).
TRIGGER
From normally open and/or open collector sink trigger inputs
INPUT 1- INPUT 8
(request to exit buttons, exit pir’s, etc.).
IN, GND
OUTPUT 1-OUTPUT 8
12 to 24 volts AC/DC trigger controlled outputs:
NC, C, NO, COM
Fail-Safe [NC positive (+) & COM Negative (-)],
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(When using AC power supplies polarity need not be observed),
NC, C, NO become form “C” 5 amp 24VAC/VDC rated dry outputs when fuses are
removed. Contacts shown in a non-triggered state.
FACP INTERFACE
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
T, + INPUT --
normally closed from an FACP output circuit (Fig. 4 through 8 , pg. 8).
FACP INTERFACE
Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting.
NC, C, NO
(This output has not been evaluated by UL).