Set receive to transmit delay, Report number of floats, Report receive to transmit delay – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions User Manual
Page 77: Error codes
77
10 Supplement
VEGABAR 82 • Modbus and Levelmaster protocol
46294-EN-131107
Set Receive to Transmit Delay
Request:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Response:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
6 characters ASCII
UuuROK
Report Number of Floats
Request:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
4 characters ASCII
UuuF
Response:
Parameter
Length
Code/Data
Set Receive to Transmit Delay
5 characters ASCII
UuuFn
n = number of measurement values
(0, 1 or 2)
Report Receive to Transmit Delay
Request:
Parameter
Length
Code/Data
Report Receive to Transmit Delay
4 characters ASCII
UuuR
Response:
Parameter
Length
Code/Data
Report Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Error codes
Error Code
Name
EE-Error
Error While Storing Data in EEPROM
FR-Error
Erorr in Frame (too short, too long, wrong data)
LV-Error