beautypg.com

3 wiring plan – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 24

background image

24

5 Connecting to power supply and bus system

VEGABAR 82 • Modbus and Levelmaster protocol

46294-EN-131107

7. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation in case of power

supply via low voltage

8. Connect the lead cable for power supply in the same way accord-

ing to the wiring plan, in addition connect the ground conductor to

the inner ground terminal when powered with mains voltage.

9. Tighten the compression nut of the cable glands. The seal ring

must completely encircle the cables

10. Screw the housing cover back on
The electrical connection is hence finished.
Information:

The terminal blocks are pluggable and can be removed from the

housing insert. To do this, lift the terminal block with a small screwdriv-

er and pull it out. When inserting the terminal block again, you should

hear it snap in.

5.3 Wiring plan

2

1

Fig. 19: Position of connection compartment (Modbus electronics) and electron-

ics compartment (sensor electronics)
1 Connection compartment

2 Electronics compartment

5 6 7 8

4...20mA

2

1

2

+

( )

(-)

1

1

Fig. 20: Electronics compartment, double chamber housing
1 Internal connection to the connection compartment

2 For display and adjustment module or interface adapter

Overview

Electronics compartment