10 Supplement
VEGABAR 82 • Modbus and Levelmaster protocol
46294-EN-131107
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x11
Byte Number
1 Byte
Slave ID
1 Byte
Run Indicator Status
1 Byte
FC43 Sub 14, Read Device Identification
With this function code, the Device Identification can be queried.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Object ID
1 Byte
0x00 to 0xFF
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Confirmity Level
1 Byte
0x01, 0x02, 0x03, 0x81, 0x82, 0x83
More follows
1 Byte
00/FF
Next Object ID
1 Byte
Object ID number
Number of Objects
1 Byte
List of Object ID
1 Byte
List of Object length
1 Byte
List of Object value
1 Byte
Depending on the Object ID
10.5 Levelmaster commands
The VEGABAR 82 is also suitable for connection to the following RTUs with Levelmaster protocol.
The Levelmaster protocol is often called "Siemens" "Tank protocol".
RTU
Protocol
ABB Totalflow
Levelmaster
Kimray DACC 2000/3000
Levelmaster
Thermo Electron Autopilot
Levelmaster
Parameters for the bus communication
The VEGABAR 82 is preset with the default values: