beautypg.com

Protocol description, Parameters for the bus communication, The vegabar 82 is preset with the default values – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 68: Start bits and data bits cannot be modified, 10 supplement

background image

68

10 Supplement

VEGABAR 82 • Modbus and Levelmaster protocol

46294-EN-131107

4

1

3

3

3

2

+

+

power supply

MODBUS

D0

D1

IS GN

D

USB

+

+

power supply

MODBUS

D0

D1

IS GN

D

USB

+

+

power supply

MODBUS

D0

D1

IS GN

D

USB

1

3 4 5

2

off on

( )

(

)

(-)

(-)

1

3 4 5

2

off on

( )

(

)

(-)

(-)

1

3 4 5

2

off on

( )

(

)

(-)

(-)

Fig. 36: Bus architecture Modbus
1 RTU

2 Connection resistor

3 Bus participant

4 Voltage supply

Protocol description

The VEGABAR 82 is suitable for connection to the following RTUs with Modbus RTU or ASCII

protocol.

RTU

Protocol

ABB Totalflow

Modbus RTU, ASCII

Bristol ControlWaveMicro

Modbus RTU, ASCII

Fisher ROC

Modbus RTU, ASCII

ScadaPack

Modbus RTU, ASCII

Thermo Electron Autopilot

Modbus RTU, ASCII

Parameters for the bus communication

The VEGABAR 82 is preset with the default values:

Parameter

Configurable Values

Default Value

Baud Rate

1200, 2400, 4800, 9600, 19200

9600

Start Bits

1

1

Data Bits

7, 8

8

Parity

None, Odd, Even

None

Stop Bits

1, 2

1

Address range Modbus

1 … 255

246

Start bits and data bits cannot be modified.