Protocol description
The VEGABAR 82 is suitable for connection to the following RTUs with Modbus RTU or ASCII
protocol.
RTU
Protocol
ABB Totalflow
Modbus RTU, ASCII
Bristol ControlWaveMicro
Modbus RTU, ASCII
Fisher ROC
Modbus RTU, ASCII
ScadaPack
Modbus RTU, ASCII
Thermo Electron Autopilot
Modbus RTU, ASCII
Parameters for the bus communication
The VEGABAR 82 is preset with the default values:
Parameter
Configurable Values
Default Value
Baud Rate
1200, 2400, 4800, 9600, 19200
9600
Start Bits
1
1
Data Bits
7, 8
8
Parity
None, Odd, Even
None
Stop Bits
1, 2
1
Address range Modbus
1 … 255
246
Start bits and data bits cannot be modified.