VEGA VEGASON 65 Foundation Fieldbus User Manual
Page 50

Input variable
M
easured value
-
V
ersion A
distance between lower edge of the flange and
product surface
-
version B, C and D
distance between lower edge of the transducer and
product surface
D
ead band
0.8
m (2.624 ft)
M
easuring range
-
L
iquids
up to 45 m (147.6 ft)
-
B
ulk solids
up to 25 m (82.02 ft)
Reference conditions to measuring accuracy (similar to DIN EN 60770-1)
R
eference conditions according to DIN EN 61298-1
-
T
emperature
+18
… +30 °C (+64 … +86 °F)
-
R
elative humidity
45 … 75 %
-
A
ir pressure
860 … 1060
mbar/86 … 106 kPa (12.5 … 15.4 psig)
O
ther reference conditions
-
R
eflector
ideal reflector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft)
-
F
alse reflections
B
iggest false echo, 20 dB smaller than the useful
echo
Measuring characteristics
U
ltrasonic frequency
18
kHz
I
nterval
> 2
s (dependent on the parameter adjustment)
B
eam angle at 3 dB
5°
A
djustment time
6)
> 3
s (dependent on the parameter adjustment)
Measuring accuracy
R
esolution, general
> 1
mm (0.039 in)
D
eviation
7)
see diagram
6)
T
ime to output the correct level (with max. 10 % deviation) after a sudden
level change.
7)
I
ncl. non-linearity, hysteresis and non-repeatability.
50
VEGASON
65 • F
oundation Fieldbus
10 S
upplement
28794
-EN