2 mounting preparations – VEGA VEGASON 65 Foundation Fieldbus User Manual

Page 14

background image

1

3

2

100%

0%

4

Fig. 4: Version B, C, D - Measuring range (operating range) and max. measuring
distance
1

full (dead band)

2

empty (max. measuring distance)

3

Measuring range

4

Reference plane

G

auge pressure in the vessel does not influence VEGASON 65. Low

pressure or vacuum does, however, damp the ultrasonic pulses. This
influences the measuring result, particularly if the level is very low.
W

ith pressures under -0.2 bar (-20 kPa) you should use a different

measuring principle, e.g. radar or guided microwave.

4.2 Mounting preparations

Warning:
M

ounting preparations must be carried out in idle condition. Non-

observance can cause damages on the electronics!

V

ersion B is supplied in two parts:

l

T

ransducer

l

E

lectronics housing

A

ssemble the version as follows:

1

L

oosen the screws on the fixing ring (4) with a hexagon spanner

(

size 4), remove the transducer tube out of the swivelling holder

2

M

ount the flange

Pressure/Vacuum

Mounting - Version B

14

VEGASON

65 • F

oundation Fieldbus

4 M

ounting

28794

-EN

-081127