Functions

The module monitors the power supply for the complete panel and regulates
battery charging as a function of time and temperature. The button has
three functions, which are dependent on the status of the battery controller
module:
-

The four module LEDs light up as a confirmation and LED test each time
the button is pressed.

-

If the batteries have a voltage of between 18 V and 21 V, the battery
loading procedure can be started manually. Please note that a power
supply must be available.

-

The 24 V switch outputs can be reset. The switch output is deactivated
if a fault occurs.

i

NOTICE!

-

Installation must only be carried out by authorized
personnel.

-

The BCM-0000-B can only be used with panel controllers
FPA-1200-MPC and MPC-xx00-B with software versions
from 2.1 onwards.

-

The total current for all connected components, including
the battery charge current, must not exceed 6 A.

-

The 24 V switch outputs must not be connected in parallel.

-

The batteries connected to BCM-0000-B must all be the
same type and have the same electrical features.

-

The length of the cable on the fault switch outputs must
not exceed 3 meters (approx. 9.8 feet).

-

The cables on the fault switch outputs must only be
installed within the housing.