beautypg.com

York 251934-YTG-J-0910 User Manual

Page 89

background image

251934-YTG-J-0910

Johnson Controls Unitary Products

89

300

(25)

208-3-60 38.0

42.9

304

267

59.4

63

4.5

38.6

0.0

None

-

-

-

145.5

175

E18

13.5

1

37.5

145.5

175

E36

27.0

2

74.9

145.5

175

E54

40.6

2

112.7

189.1

200

E72

54.1

2

150.2

198.4

225

230-3-60 38.0

42.9

304

267

59.4

62.9

4.3

38.6

0.0

None

-

-

-

145.1

175

E18

18.0

1

43.3

145.1

175

E36

36.0

2

86.6

156.5

175

E54

54.0

2

129.9

178.2

200

E72

72.0

2

173.2

221.5

250

460-3-60 18.9

18.5 162.6

130

29.5

29

2.2

19.3

0.0

None

-

-

-

68.5

80

E18

18.0

1

21.7

68.5

80

E36

36.0

2

43.3

78.3

80

E54

54.0

2

65.0

89.1

100

E72

72.0

2

86.6

110.7

125

575-3-60 15.1

15.3 135.9

114

23.7

24

1.7

15.4

0.0

None

-

-

-

55.3

70

E18

18.0

1

17.3

55.3

70

E36

36.0

2

34.6

62.6

70

E54

54.0

2

52.0

71.2

80

E72

72.0

2

69.3

88.5

100

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

ZF180-300 - Hi Static Drive Without Powered Convenience Outlet (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max Fuse

2

/

Breaker

3

Size

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

Model

kW

Stages

Amps

C1

C2

C1

C2

C1

C2