York 251934-YTG-J-0910 User Manual
Page 22
251934-YTG-J-0910
22
Johnson Controls Unitary Products
115°F
125°F
3750
77
180.3
17.1
78.5
67.6
49.8
-
-
-
166.8
18.9
68.4
61.1
43.5
-
-
-
72
167.2
16.9
111.3
93.5
75.7
57.9
-
-
154.4
18.7
105.1
87.6
70.0
52.4
-
-
67
154.0
16.8
144.1
119.5
101.7
83.9
66.1
-
141.9
18.6
141.9
114.0
96.5
78.9
61.3
-
62
143.0
16.6
143.0
143.0
124.7
106.9
89.1
71.3
131.7
18.4
131.7
131.7
120.0
100.6
83.0
65.5
4500
77
186.6
17.0
95.7
75.3
54.8
-
-
-
172.7
18.8
89.1
68.5
48.1
-
-
-
72
173.0
16.8
124.3
103.8
83.4
62.9
-
-
159.8
18.6
118.0
97.7
77.3
57.0
-
-
67
159.5
16.7
152.9
132.4
111.9
91.5
71.0
-
146.9
18.4
146.9
126.9
106.6
86.2
65.9
-
62
148.0
16.5
148.0
148.0
137.3
116.8
96.4
75.9
136.4
18.3
136.4
136.4
130.6
110.2
89.9
69.6
57
149.2
16.6
149.2
149.2
132.8
112.4
91.9
71.5
139.1
18.4
139.1
139.1
123.0
102.7
82.3
62.0
5250
77
193.0
16.8
113.0
83.0
59.8
-
-
-
178.6
18.6
109.8
75.8
52.7
-
-
-
72
178.9
16.7
137.3
114.2
91.0
67.9
-
-
165.3
18.4
130.9
107.8
84.7
61.6
-
-
67
164.9
16.5
161.6
145.3
122.2
99.1
76.0
-
152.0
18.3
152.0
139.8
116.7
93.6
70.5
-
62
153.1
16.4
153.1
153.1
149.9
126.8
103.7
80.5
141.1
18.1
141.1
141.1
141.1
119.9
96.8
73.7
57
154.2
16.5
154.2
154.2
145.0
121.9
98.8
75.6
143.8
18.2
143.8
143.8
134.7
111.6
88.5
65.4
6000
77
199.3
16.7
130.3
90.7
64.9
-
-
-
184.5
18.5
130.5
83.2
57.3
-
-
-
72
184.8
16.6
150.3
124.5
98.7
72.9
-
-
170.8
18.3
143.7
117.9
92.0
66.2
-
-
67
170.3
16.4
170.3
158.3
132.5
106.7
80.9
-
157.0
18.1
157.0
152.6
126.8
100.9
75.1
-
62
158.1
16.3
158.1
158.1
162.5
136.7
110.9
85.1
145.8
18.0
145.8
145.8
145.8
129.5
103.6
77.8
57
159.3
16.3
159.3
159.3
157.2
131.4
105.6
79.8
148.6
18.1
148.6
148.6
146.4
120.5
94.7
68.8
6600
72
186.1
16.6
158.7
131.5
104.3
77.0
-
-
171.7
18.3
152.1
124.8
97.5
70.2
-
-
67
171.5
16.4
171.5
165.5
140.0
112.7
85.5
-
157.9
18.1
157.9
157.9
134.2
106.9
79.7
-
62
159.2
16.3
159.2
159.2
161.4
134.2
106.9
79.7
146.6
18.0
146.6
146.6
146.6
124.1
96.8
69.5
57
160.4
16.4
160.4
160.4
159.4
132.1
104.9
77.7
149.4
18.1
149.4
149.4
148.3
121.1
93.8
66.5
7200
72
187.3
16.6
167.1
138.5
109.8
81.2
-
-
172.7
18.3
160.4
131.6
102.9
74.2
-
-
67
172.6
16.4
172.6
172.6
147.4
118.8
90.1
-
158.8
18.2
158.8
158.8
141.7
113.0
84.2
-
62
160.3
16.3
160.3
160.3
160.3
131.6
102.9
74.3
147.4
18.0
147.4
147.4
147.4
118.7
90.0
61.2
57
161.5
16.4
161.5
161.5
161.5
132.8
104.2
75.5
150.3
18.1
150.3
150.3
150.3
121.6
92.8
64.1
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZJ180 (15 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65