York 251934-YTG-J-0910 User Manual
Page 44
251934-YTG-J-0910
44
Johnson Controls Unitary Products
115°F
125°F
4375
77
206.1
20.8
80.0
70.9
52.9
-
-
-
190.0
22.6
66.6
63.7
46.3
-
-
-
72
190.8
20.5
121.1
103.1
85.1
67.1
-
-
175.7
22.2
113.6
96.1
78.7
61.2
-
-
67
175.5
20.2
162.1
135.3
117.3
99.3
81.3
-
161.5
21.9
160.3
128.5
111.0
93.5
76.0
-
62
167.3
20.0
167.3
166.3
136.4
118.4
100.5
82.5
157.2
21.8
157.2
155.7
124.1
106.6
89.1
71.6
5250
77
213.6
20.8
101.5
80.1
58.6
-
-
-
196.9
22.5
94.7
73.3
51.9
-
-
-
72
197.7
20.5
137.2
115.8
94.3
72.8
-
-
182.2
22.2
130.8
109.4
88.0
66.7
-
-
67
181.8
20.1
172.9
151.5
130.0
108.5
87.1
-
167.5
21.8
166.9
145.5
124.2
102.8
81.4
-
62
173.3
20.0
173.3
172.7
151.2
129.8
108.3
86.9
163.0
21.7
163.0
162.0
139.0
117.6
96.3
74.9
57
172.0
20.0
172.0
172.0
153.1
131.7
110.2
88.7
161.7
21.8
161.7
161.7
141.6
120.2
98.8
77.5
6125
77
221.1
20.7
123.0
89.2
64.3
-
-
-
203.9
22.4
122.7
82.9
57.5
-
-
-
72
204.6
20.4
153.4
128.4
103.5
78.6
-
-
188.7
22.1
147.9
122.7
97.4
72.2
-
-
67
188.2
20.1
183.7
167.6
142.7
117.8
92.9
-
173.4
21.8
173.4
162.6
137.3
112.1
86.9
-
62
179.4
19.9
179.4
179.1
166.0
141.1
116.2
91.3
168.7
21.6
168.7
168.3
153.8
128.6
103.4
78.2
57
178.0
20.0
178.0
178.0
168.1
143.2
118.3
93.3
167.5
21.7
167.5
167.5
156.7
131.5
106.2
81.0
7000
77
228.5
20.7
144.5
98.4
70.1
-
-
-
210.9
22.4
150.7
92.5
63.1
-
-
-
72
211.5
20.4
169.5
141.1
112.7
84.4
-
-
195.1
22.0
165.0
135.9
106.8
77.7
-
-
67
194.5
20.1
194.5
183.8
155.4
127.1
98.7
-
179.4
21.7
179.4
179.4
150.5
121.4
92.3
-
62
185.5
19.9
185.5
185.5
180.8
152.4
124.1
95.7
174.5
21.6
174.5
174.5
168.7
139.6
110.5
81.4
57
184.0
19.9
184.0
184.0
183.1
154.7
126.3
97.9
173.2
21.6
173.2
173.2
171.8
142.7
113.6
84.5
7875
72
212.1
20.5
176.1
147.0
117.9
88.7
-
-
195.2
22.1
170.0
140.6
111.3
81.9
-
-
67
195.0
20.1
195.0
189.7
162.5
133.4
104.2
-
179.4
21.7
179.4
179.4
156.8
127.4
98.0
-
62
185.9
20.0
185.9
185.9
183.6
154.5
125.4
96.2
174.6
21.6
174.6
174.6
171.7
142.3
112.9
83.5
57
184.5
20.0
184.5
184.5
184.0
154.9
125.8
96.6
173.3
21.7
173.3
173.3
172.6
143.2
113.8
84.4
8750
72
212.6
20.5
182.7
152.9
123.0
93.1
-
-
195.2
22.2
175.0
145.4
115.7
86.0
-
-
67
195.6
20.2
195.6
195.6
169.6
139.7
109.8
-
179.4
21.8
179.4
179.4
163.1
133.4
103.8
-
62
186.4
20.0
186.4
186.4
186.4
156.6
126.7
96.8
174.7
21.7
174.7
174.7
174.7
145.0
115.3
85.7
57
185.0
20.1
185.0
185.0
185.0
155.1
125.2
95.3
173.3
21.7
173.3
173.3
173.3
143.7
114.0
84.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF210 (17.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65