beautypg.com

Sound power rating, Capacity ratings - (ari 210/240), Gas heat ratings – York SUNLINE 2000 DM 048 User Manual

Page 8: 2 stage gas heat ratings

background image

292454-YTG-B-0507

8

Unitary Products Group

TABLE 1: SOUND POWER RATING

1

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (db 10

-12

Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@

10Ft.

2

IWG

SPEED

KW

63

125

250

500

1,000

2,000

4,000

8,000

036

1,200

0.6

LOW

0.60

84

84

74

67

69

62

57

52

74

41

048

1,600

0.55

HIGH

0.80

85

85

75

68

70

63

58

53

75

42

060

2,000

0.45

HIGH

1.00

86

86

76

69

71

64

59

54

76

43

072

2,200

0.3

HIGH

1.35

87

87

77

70

72

65

60

55

77

44

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The

dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 210/240)

1

1. 80/67°F Indoor and 95°F outdoor.

MODEL

MBH

EER

2

2. EER = Energy Efficiency Ratio at full load - the cooling

capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).

SEER

3

3. SEER = Seasonal Energy Efficiency Ratio.

DM036

36.0

9.1

10.0

DM048

47.4

9.0

10.0

DM060

59.0

9.1

10.0

DM072

72.0

9.0

-

TABLE 3: GAS HEAT RATINGS

1

1. All units are single-stage heating.

MODEL

MBH

INPUT

MBH

OUTPUT

AFUE

(%)

TEMP

RISE ºF

DM036N04
DM036N08

50

100

40
80

80.9
80.5

15 - 45
40 - 70

DM048N06
DM048N10

75

125

60

100

80.9
80.3

25 - 55
45 - 75

DM060N08
DM060N10

100
125

80

100

80.5
80.3

25 - 55
35 - 65

DM072N08
DM072N10

100
125

80

100

80.5
80.3

25 - 55
35 - 65

TABLE 4: 2 STAGE GAS HEAT RATINGS

MODEL

1

1. Models are 3Ø only.

MBH INPUT

MBH OUTPUT

STEADY STATE EFFICIENCY

RISE

MINIMUM HEATING

AIRFLOW (CFM)

1

ST

STAGE 2

ND

STAGE 1

ST

STAGE 2

ND

STAGE

1

ST

STAGE

2

ND

STAGE

MIN.

MAX.

DM036D06

45

75

35.8

60.8

79.4

81.1

35

70

790

DM036D10

69

115

55.2

92

80.0

80.2

55

90

950

DM048D06

45

75

35.7

60.8

79.4

81.1

25

70

790

DM048D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DM060D06

45

75

35.8

60.8

79.4

81.1

35

70

1010

DM060D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DM072D06

45

75

35.8

60.8

79.4

81.1

35

70

1230

DM072D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

This manual is related to the following products: