York SUNLINE 2000 DM 048 User Manual
Page 20
292454-YTG-B-0507
20
Unitary Products Group
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
ELECTRIC HEATER
MODEL NO.
HEATER
KW
HEATER
AMPS
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
DM060
(5.0)
208-3-60
16.0
125.0
1.3
6.6
0.0
None
--
--
27.9
35
2CE04510525
2
4
11.1
27.9
35
2CE04510725
2
5.6
15.5
27.9
35
2CE04511025
8
22.2
36
40
2CE04511525
11.9
33.0
49.5
50
2CE04512025
15.9
44.1
63.4
70
2CE04513025
22.2
61.6
85.3
90
230-3-60
16.0
125.0
1.3
6.6
0.0
None
--
--
27.9
35
2CE04510525
2
5.3
12.7
27.9
35
2CE04510725
2
7.5
18.0
30.8
40
2CE04511025
10.6
25.5
40.1
45
2CE04511525
15.9
38.2
56.1
60
2CE04512025
21.2
51.0
72
80
2CE04513025
29.6
71.2
97.3
100
460-3-60
8.0
66.5
0.8
3.3
0.0
None
--
--
14.1
20
2CE04510746
2
6.8
8.2
14.3
20
2CE04511046
2
10.1
12.1
19.3
20
2CE04511546
2
13.6
16.4
24.6
25
2CE04512046
2
19.5
23.5
33.4
35
2CE04513046
2
28.8
34.6
47.4
50
575-3-60
6.4
50.0
0.8
3.3
0.0
None
--
--
11.3
15
2CE04511058
10.6
10.2
16
20
2CE04511558
15.9
15.3
22.4
25
2CE04512058
21.2
20.4
28.8
30
2CE04513058
30.4
29.3
39.9
40
DM072
(6.0)
208-3-60
18.9
146.0
1.3
6.8
0.0
None
--
--
31.7
40
2CE04510525
2
4
11.1
31.7
40
2CE04510725
2
5.6
15.5
31.7
40
2CE04511025
8
22.2
36.3
50
2CE04511525
11.9
33.0
49.8
50
2CE04512025
15.9
44.1
63.7
70
2CE04513025
22.2
61.6
85.5
90
230-3-60
18.9
146.0
1.3
6.8
0.0
None
--
--
31.7
40
2CE04510525
2
5.3
12.7
31.7
40
2CE04510725
2
7.5
18.0
31.7
40
2CE04511025
10.6
25.5
40.4
50
2CE04511525
15.9
38.2
56.3
60
2CE04512025
21.2
51.0
72.2
80
2CE04513025
29.6
71.2
97.5
100
460-3-60
9.5
73.0
0.8
3.6
0.0
None
--
--
16.3
25
2CE04510746
2
6.8
8.2
16.3
25
2CE04511046
2
10.1
12.1
19.7
25
2CE04511546
2
13.6
16.4
24.9
25
2CE04512046
2
19.5
23.5
33.8
35
2CE04513046
2
28.8
34.6
47.8
50
575-3-60
7.6
58.4
0.8
3.6
0.0
None
--
--
13
15
2CE04511058
10.6
10.2
16.3
20
2CE04511558
15.9
15.3
22.7
25
2CE04512058
21.2
20.4
29.1
30
2CE04513058
30.4
29.3
40.2
40
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 17: ELECTRICAL DATA - DM036-072 DIRECT DRIVE W/O POWERED CONV. OUTLET (CONT.)