Supply air blower performance (3 ton, Belt drive) - side duct application – York SUNLINE 2000 DM 048 User Manual
Page 13
292454-YTG-B-0507
Unitary Products Group
13
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
1700
835
705
880
745
923
795
969
860
1013
970
-
-
-
-
1600
811
655
854
695
898
740
942
790
986
840
1029
900
-
-
1500
782
610
827
650
871
685
917
730
960
775
1003
825
1046
905
1400
-
-
798
595
844
640
889
680
932
720
975
765
1018
790
1300
-
-
-
-
816
590
862
635
907
675
951
715
995
750
1200
-
-
-
-
-
-
834
585
881
630
927
665
970
705
1100
-
-
-
-
-
-
809
550
855
590
900
625
942
665
1000
-
-
-
-
-
-
782
510
829
545
872
858
919
625
900
-
-
-
-
-
-
-
-
797
500
843
540
890
580
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
1700
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1600
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1400
1055
875
-
-
-
-
-
-
-
-
-
-
-
-
1300
1036
780
1066
850
-
-
-
-
-
-
-
-
-
-
1200
1011
735
1047
765
1075
800
-
-
-
-
-
-
-
-
1100
987
690
1028
720
1060
750
1084
775
-
-
-
-
-
-
1000
963
655
1005
680
1040
695
1068
715
1089
735
-
-
-
-
900
936
615
980
645
1020
660
1050
670
1053
680
1090
690
-
-
0.60
0.70
0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20
0.30
0.40
0.50
UNIT
TONNAGE
AIR
FLOW
CFM
3
1,2
UNIT
TONNAGE
AIR
FLOW
CFM
3
1
, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.