beautypg.com

21 physical data, 22 electric heat correction factors, 23 voltage limitations – York SUNLINE 2000 DM 048 User Manual

Page 27

background image

292454-YTG-B-0507

Unitary Products Group

27

TABLE 21: PHYSICAL DATA

MODELS

DM

036

048

060

072

EVAPORATOR

BLOWER

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

12 X 10

12 X 11

Fan Motor HP (Direct Drive)

1/2

3/4

1

1

Fan Motor HP (Belt Drive)

1 1/2

1 1/2

1 1/2

1 1/2

EVAPORATOR

COIL

Rows Deep

3

3

3

4

Fins Per Inch

13

13

13

13

Face Area (Sq. Ft.)

3.6

4.3

5.1

5.1

CONDENSER

FANS

Propeller Dia. (in.)

24

24

24

24

Fan Motor Hp

1/4

1/4

1/4

1/4

Nom. CFM

3400

3400

3400

3400

CONDENSER

COILS

Rows Deep

1

1

1

2

Fins Per Inch

16

16

22

16

Face Area (Sq. Ft.)

17.1

17.1

17.1

16.7

COMPRESSOR

(Qty. Per Unit)

Quantity / Type

1 / Recip

1 / Scroll

1 / Scroll

1 / Scroll

AIR

FILTERS

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

2

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

1

Total Face Area (sq. ft.)

6.3

6.3

6.3

6.3

CHARGE

Refrigerant 22

(lbs./oz.)

5/8

6/8

6/8

10/0

TABLE 22: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP.

MULTIPLIER

208

208

0.75

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 23: VOLTAGE LIMITATIONS

1

1. Utilization Range “A” in accordance with ARI Standard

110.

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

540

630

This manual is related to the following products: