15 static resistances, 16 electric heater cfm limitations – York SUNLINE 2000 DM 048 User Manual
Page 18
292454-YTG-B-0507
18
Unitary Products Group
TABLE 15: STATIC RESISTANCES
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.30
7-15KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.19
0.22
20-30KW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
0.19
0.22
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
COOLING ONLY
2
RESISTANCE, IWG
CFM
DESCRIPTION
ECONOMIZER
1 3
BOTTOM DUCT CONNECTIONS
1
ELECTRIC
HEATERS
1
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
TABLE 16: ELECTRIC HEATER CFM LIMITATIONS
UNITMODEL SIZE NOMINAL
TONS
VOLTAGE
MINIMUM SUPPLY AIR CFM
HEATER SIZE NOMINAL KW
5
7
10
15
20
30
3
208/230-3-60
1100
1100
1200
1200
1300
-
460-3-60
-
1100
1200
1200
1300
-
575-3-60
-
-
1200
1200
1300
-
4
208/230-3-60
1300
1300
1300
1300
1300
-
460-3-60
-
1300
1300
1300
1300
-
575-3-60
-
-
1300
1300
1400
-
5
208/230-3-60
1600
1600
1600
1600
1600
1600
460-3-60
-
1600
1600
1600
1600
1600
575-3-60
-
1600
1600
1600
1600
1800
6
208/230-3-60
1800
1800
1800
1800
1800
1800
460-3-60
-
1800
1800
1800
1800
1800
575-3-60
-
-
1800
1800
1800
1800