background image

COOLING CAPACITIES (m

3

/s Air Flow) - 240 UNITS

Air On

Evaporator Coil

Total

Cap.

1

kW

Power

Input

2

kW

Sensible Capacity

1

, kW

Entering Dry Bulb Temp.,

°

C

m

3

/s

WB

°

C

32

30

28

26

24

22

@27

°

C Air Temperature on Condenser Coil

4.40

23

80.4

19.0

74

65

55

46

37

-

21

77.6

18.8

78

70

61

52

43

33

19

74.8

18.6

75

75

67

57

48

39

17

72.4

18.4

72

72

71

62

53

44

15

70.0

18.1

70

70

70

65

56

47

3.80

23

76.9

18.8

68

60

52

44

36

-

21

74.3

18.6

73

65

57

49

41

33

19

71.6

18.4

72

70

62

54

46

38

17

69.3

18.2

69

69

67

59

51

43

15

67.0

17.9

67

67

67

63

55

47

2.80

23

71.2

18.5

56

50

44

37

31

-

21

68.7

18.3

60

54

48

42

36

30

19

66.3

18.1

65

59

52

46

40

34

17

64.1

17.9

64

62

56

50

44

38

15

62.0

17.6

62

62

60

54

47

41

@35

°

C Air Temperature on Condenser Coil

4.40

23

74.9

21.0

71

61

52

43

34

-

21

72.3

20.7

72

68

58

49

40

31

19

69.8

20.4

70

70

65

55

46

37

17

67.4

20.1

67

67

67

58

49

40

15

65.0

19.9

65

65

65

60

51

42

3.80

23

71.3

20.7

65

57

49

41

33

-

21

68.9

20.5

69

62

54

46

38

30

19

66.4

20.2

66

66

60

52

44

36

17

64.2

19.9

64

64

63

55

47

39

15

61.9

19.7

62

62

62

58

50

42

2.80

23

65.4

20.4

52

46

40

34

28

-

21

63.1

20.1

57

51

45

39

33

27

19

60.9

19.8

61

56

50

44

38

31

17

58.8

19.6

59

58

52

46

40

34

15

56.7

19.3

57

57

54

48

42

36

@46

°

C Air Temperature on Condenser Coil

4.40

23

66.4

23.4

65

56

47

38

29

-

21

63.3

22.9

63

62

53

44

35

26

19

60.2

22.3

60

60

60

51

41

32

17

59.0

22.3

59

59

59

53

43

34

15

57.8

22.2

58

58

58

53

44

35

3.80

23

63.8

23.3

60

52

44

36

28

-

21

60.8

22.7

61

58

50

42

34

26

19

57.8

22.2

58

58

56

48

40

32

17

56.7

22.1

57

57

57

50

42

34

15

55.5

22.1

56

56

56

52

44

35

2.80

23

59.4

23.1

49

42

36

30

24

-

21

56.6

22.5

54

47

41

35

29

23

19

53.8

22.0

54

53

46

40

34

28

17

52.8

21.9

53

53

48

42

36

30

15

51.7

21.9

52

52

49

43

37

31

1

These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the

supply air blower motor.

2

These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

530.26-TG3YI

6

Unitary Products Group

This manual is related to the following products: