Blower performance – York SUNLINE 2000 D3CG User Manual

Page 10

background image

BLOWER

SPEED,

RPM

MOTOR

PULLEY

(TURNS

OPEN)*

AIRFLOW

4450 CFM

5190 CFM

5930 CFM

6565 CFM

7200 CFM

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

845

6.0

0.8

2.5

2.2

0.6

2.7

2.5

0.3

3.2

2.8

0.1

3.6

3.2

-

-

-

885

5.0

1.0

2.6

2.3

0.7

2.9

2.6

0.5

3.4

3.0

0.2

3.8

3.4

-

-

-

925

4.0

1.1

2.7

2.4

0.9

3.1

2.7

0.6

3.6

3.2

0.4

4.1

3.7

0.1

4.7

4.2

960

3.0

1.2

2.8

2.5

1.0

3.2

2.9

0.8

3.8

3.4

0.5

4.3

3.9

0.3

5.0

4.5

1000

2.0

1.4

2.9

2.6

1.2

3.4

3.1

0.9

4.0

3.6

0.7

4.7

4.2

0.4

5.3

4.8

1040

1.0

1.6

3.1

2.8

1.3

3.7

3.3

1.1

4.3

3.9

0.8

5.0

4.4

0.6

5.7

5.1

STANDARD DRIVE (CFM)

BLOWER

SPEED,

RPM

MOTOR

PULLEY

(TURNS

OPEN)*

AIRFLOW

4450 CFM

5190 CFM

5930 CFM

6565 CFM

7200 CFM

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

1030

6.0

1.5

3.1

2.7

1.3

3.6

3.2

1.0

4.3

3.8

0.8

4.9

4.4

0.5

5.6

5.0

1070

5.0

1.7

3.3

2.9

1.4

3.8

3.4

1.2

4.5

4.1

1.0

5.2

4.7

-

-

-

1115

4.0

1.9

3.5

3.1

1.6

4.1

3.7

1.4

4.9

4.4

1.2

5.6

5.0

-

-

-

1155

3.0

2.0

3.7

3.3

1.8

4.4

4.0

1.6

5.2

4.7

-

-

-

-

-

-

1200

2.0

2.2

4.0

3.6

2.0

4.8

4.3

1.7

5.6

5.0

-

-

-

-

-

-

1240

1.0

2.4

4.3

3.8

2.2

5.1

4.6

-

-

-

-

-

-

-

-

-

NOTES:

1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat.
2. Refer to Page 12 for the resistance values for all other unit options or applications.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

*

Do NOT close pulley below minimum turns open.

HIGH SPEED DRIVE (CFM)

BLOWER

SPEED,

RPM

MOTOR

PULLEY

(TURNS

OPEN)*

AIRFLOW

2.10 m

3

/s

2.45 m

3

/s

2.80 m

3

/s

3.10 m

3

/s

3.40 m

3

/s

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

845

6.0

206

1.8

2.2

146

2.0

2.5

80

2.4

2.8

18

2.7

3.2

-

-

-

885

5.0

242

1.9

2.3

183

2.2

2.6

117

2.5

3.0

56

2.9

3.4

-

-

-

925

4.0

278

2.0

2.4

220

2.3

2.7

155

2.7

3.2

94

3.1

3.7

28

3.5

4.2

960

3.0

311

2.1

2.5

253

2.4

2.9

189

2.8

3.4

128

3.2

3.9

63

3.7

4.5

1000

2.0

349

2.2

2.6

292

2.6

3.1

228

3.0

3.6

168

3.5

4.2

103

4.0

4.8

1040

1.0

387

2.3

2.8

331

2.7

3.3

268

3.2

3.9

209

3.7

4.4

144

4.3

5.1

STANDARD DRIVE (m /s)

3

BLOWER

SPEED,

RPM

MOTOR

PULLEY

(TURNS

OPEN)*

AIRFLOW

2.10 m

3

/s

2.45 m

3

/s

2.80 m

3

/s

3.10 m

3

/s

3.40 m

3

/s

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

1030

6.0

378

2.3

2.7

321

2.7

3.2

258

3.2

3.8

199

3.6

4.4

134

4.2

5.0

1070

5.0

417

2.4

2.9

361

2.9

3.4

299

3.4

4.1

240

3.9

4.7

-

-

-

1115

4.0

461

2.6

3.1

407

3.1

3.7

345

3.7

4.4

286

4.2

5.0

-

-

-

1155

3.0

502

2.8

3.3

448

3.3

4.0

387

3.9

4.7

-

-

-

-

-

-

1200

2.0

548

3.0

3.6

495

3.6

4.3

435

4.2

5.0

-

-

-

-

-

-

1240

1.0

590

3.2

3.8

538

3.8

4.6

-

-

-

-

-

-

-

-

-

HIGH SPEED DRIVE (m /s)

3

BLOWER PERFORMANCE

(D*CG180 UNIT SUPPLY AIR) -

w/DOWNFLOW DUCT APPLICATIONS

530.26-TG3YI

10

Unitary Products Group