beautypg.com

Ratings, Sunline 2000, Capacity ratings - cooling / electric heating – York SUNLINE 2000 D3CG User Manual

Page 3: Capacity ratings - gas heating

background image

RATINGS

®

SUNLINE 2000

MODEL DCG

(Gas Heating)

(OPTION / ACCESS.) DCE UNITS

D*CG UNITS

(OPTION / ACCESSORY)

THROWAWAY

ALUMINIZED STEEL

FEMALE

Model

Rating

1

Point

Total Output,

Mbh / kW

Total Input,

kW

COP

2

EER

3

Sensible Output,

Mbh / kW

Latent Output,

Mbh / kW

Electric Heat4

Nominal Capacity,

kW

D3CE180

T1

159 / 46.6

18.2

2.60

8.80

132 / 38.7

26.9 / 7.9

T2

142 / 41.7

20.0

2.10

7.15

141 / 41.2

1.6 / 0.5

18, 36, 54, 72

T3

152 / 44.6

16.4

2.75

9.40

119 / 34.9

33.2 / 9.7

D3CE240

T1

210 / 61.5

24.8

2.50

8.50

176 / 51.5

34.0 / 10.0

T2

182 / 53.3

27.1

2.00

6.75

182 / 53.3

0.0 / 0.0

18, 36, 54, 72

T3

196 / 57.5

22.2

2.60

8.80

152 / 44.6

42.6 / 12.5

1

T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.

2

COP = Coefficient of Performance - total output kW divided by the total input kW.

3

EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.

4

Heaters available as factory-installed options or field-installed accessories - all with single point power supply.

CAPACITY RATINGS - Cooling / Electric Heating

Model

Cooling Capacity,

Mbh / kW

Gas Heat Capacity

Input (Net)

Mbh / kW

Output

Mbh / kW

Gas Rate*

cfh / m

3

/h

Temp. Rise (

°

F /

°

C)

At Full Input

Min.

Max.

D3CG180N320

180 / 52.7

291 / 85.2

258 / 75.6

302 / 8.5

30 / 17

60 / 33

D3CG240N320

240 / 70.3

NOTE: Gas Heaters are shipped available for natural gas, but can be converted to L.P. / propane gas with a field-installed conversion accessory. All gas units are two-stage heating.
First stage is 50% of total.

*

Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m

3

).

CAPACITY RATINGS - Gas Heating

530.26-TG3YI

Unitary Products Group

3

This manual is related to the following products: