Ratings, Sunline 2000, Capacity ratings - cooling / electric heating – York SUNLINE 2000 D3CG User Manual
Page 3: Capacity ratings - gas heating
RATINGS
®
SUNLINE 2000
MODEL DCG
(Gas Heating)
(OPTION / ACCESS.) DCE UNITS
D*CG UNITS
(OPTION / ACCESSORY)
THROWAWAY
ALUMINIZED STEEL
FEMALE
Model
Rating
1
Point
Total Output,
Mbh / kW
Total Input,
kW
COP
2
EER
3
Sensible Output,
Mbh / kW
Latent Output,
Mbh / kW
Electric Heat4
Nominal Capacity,
kW
D3CE180
T1
159 / 46.6
18.2
2.60
8.80
132 / 38.7
26.9 / 7.9
T2
142 / 41.7
20.0
2.10
7.15
141 / 41.2
1.6 / 0.5
18, 36, 54, 72
T3
152 / 44.6
16.4
2.75
9.40
119 / 34.9
33.2 / 9.7
D3CE240
T1
210 / 61.5
24.8
2.50
8.50
176 / 51.5
34.0 / 10.0
T2
182 / 53.3
27.1
2.00
6.75
182 / 53.3
0.0 / 0.0
18, 36, 54, 72
T3
196 / 57.5
22.2
2.60
8.80
152 / 44.6
42.6 / 12.5
1
T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
2
COP = Coefficient of Performance - total output kW divided by the total input kW.
3
EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
4
Heaters available as factory-installed options or field-installed accessories - all with single point power supply.
CAPACITY RATINGS - Cooling / Electric Heating
Model
Cooling Capacity,
Mbh / kW
Gas Heat Capacity
Input (Net)
Mbh / kW
Output
Mbh / kW
Gas Rate*
cfh / m
3
/h
Temp. Rise (
°
F /
°
C)
At Full Input
Min.
Max.
D3CG180N320
180 / 52.7
291 / 85.2
258 / 75.6
302 / 8.5
30 / 17
60 / 33
D3CG240N320
240 / 70.3
NOTE: Gas Heaters are shipped available for natural gas, but can be converted to L.P. / propane gas with a field-installed conversion accessory. All gas units are two-stage heating.
First stage is 50% of total.
*
Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m
3
).
CAPACITY RATINGS - Gas Heating
530.26-TG3YI
Unitary Products Group
3