York PREDATOR BP 090 User Manual
Page 20
259336-YTG-B-0606
20
Unitary Products Group
TABLE 21: BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - SIDE DUCT (IMPERIAL)
ESP
(iwg)
Turns Open
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4960
2495
2.68
0.6
-
-
-
-
-
-
-
-
-
-
-
-
5091
2745
2.94
4646
2314
2.48
0.8
-
-
-
-
-
-
-
-
-
5078
2937
3.15
4839
2584
2.77
4347
2153
2.31
1.0
-
-
-
-
-
-
5075
3117
3.34
4767
2730
2.93
4487
2377
2.55
3946
1942
2.08
1.2
-
-
-
5068
3308
3.55
4742
2881
3.09
4427
2513
2.69
4108
2159
2.32
3501
1723
1.85
1.4
5079
3595
3.86
4787
3105
3.33
4452
2713
2.91
4012
2259
2.42
3665
1926
2.07
-
-
-
1.6
4739
3316
3.56
4482
2892
3.10
4098
2474
2.65
3543
2006
2.15
3057
1642
1.76
-
-
-
1.8
4461
3111
3.34
4070
2621
2.81
3552
2160
2.32
-
-
-
-
-
-
-
-
-
2.0
3997
2782
2.98
3400
2219
2.38
-
-
-
-
-
-
-
-
-
-
-
-
2.2
3496
2480
2.66
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 22: BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - SIDE DUCT (METRIC)
ESP
(Pa)
Turns Open
0
1
2
3
4
5
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.34
2.50
2.00
149
-
-
-
-
-
-
-
-
-
-
-
-
2.40
2.75
2.20
2.19
2.31
1.85
199
-
-
-
-
-
-
-
-
-
2.40
2.94
2.35
2.28
2.58
2.07
2.05
2.15
1.72
249
-
-
-
-
-
-
2.40
3.12
2.49
2.25
2.73
2.18
2.12
2.38
1.90
1.86
1.94
1.55
299
-
-
-
2.39
3.31
2.65
2.24
2.88
2.30
2.09
2.51
2.01
1.94
2.16
1.73
1.65
1.72
1.38
349
2.40
3.60
2.88
2.26
3.11
2.48
2.10
2.71
2.17
1.89
2.26
1.81
1.73
1.93
1.54
-
-
-
399
2.24
3.32
2.65
2.12
2.89
2.31
1.93
2.47
1.98
1.67
2.01
1.60
1.44
1.64
1.31
-
-
-
448
2.11
3.11
2.49
1.92
2.62
2.10
1.68
2.16
1.73
-
-
-
-
-
-
-
-
-
498
1.89
2.78
2.23
1.60
2.22
1.78
-
-
-
-
-
-
-
-
-
-
-
-
548
1.65
2.48
1.98
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-