York PREDATOR BP 090 User Manual
Page 15

259336-YTG-B-0606
Unitary Products Group
15
TABLE 9: HEATING APPLICATION DATA 10 TON HP HEAT (IMPERIAL)
CFM
ID DB
CAP & kW
OUTDOOR TEMPERATURE (°F) (72% RH)
-10
0
10
20
30
40
50
60
3000
55
MBH
21.2
34.2
47.3
60.3
73.3
86.4
99.4
112.4
KW
6.0
6.4
6.8
7.1
7.5
7.9
8.3
8.6
70
MBH
28.9
42.0
55.0
68.0
81.0
94.1
107.1
120.1
KW
7.4
7.8
8.1
8.5
8.9
9.2
9.6
10.0
80
MBH
30.0
43.0
56.1
69.1
82.1
95.2
108.2
121.2
KW
8.3
8.7
9.0
9.4
9.8
10.1
10.5
10.9
4000
55
MBH
23.8
36.8
49.8
62.9
75.9
88.9
102.0
115.0
KW
5.5
5.9
6.2
6.6
7.0
7.4
7.7
8.1
70
MBH
31.3
44.3
57.3
70.3
83.4
96.4
109.4
122.5
KW
6.8
7.1
7.5
7.9
8.3
8.6
9.0
9.4
80
MBH
32.6
45.6
58.7
71.7
84.7
97.8
110.8
123.8
KW
7.8
8.1
8.5
8.9
9.2
9.6
10.0
10.4
5000
55
MBH
22.7
35.8
48.8
61.8
74.9
87.9
100.9
113.9
KW
5.0
5.4
5.7
6.1
6.5
6.8
7.2
7.6
70
MBH
30.5
43.5
56.5
69.6
82.6
95.6
108.6
121.7
KW
6.3
6.7
7.1
7.5
7.8
8.2
8.6
8.9
80
MBH
31.5
44.6
57.6
70.6
83.7
96.7
109.7
122.8
KW
7.2
7.6
8.0
8.3
8.7
9.1
9.5
9.8
THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.