TABLE 8: HEATING APPLICATION DATA 7 1/2 TON HP HEAT (METRIC)
M
3
S
ID DB
(C)
KW
OUTDOOR TEMPERATURE (C)
-23
-18
-12
-7
-1
4
10
16
1.06
12.8
Capacity
7.7
9.3
11.3
13.8
16.8
20.5
24.9
30.4
Power Input
4.4
4.7
4.9
5.1
5.4
5.6
5.8
6.1
21.1
Capacity
6.6
8.3
10.3
12.8
15.8
19.4
23.9
29.3
Power Input
5.2
5.4
5.7
5.9
6.1
6.4
6.6
6.9
26.7
Capacity
5.5
7.2
9.2
11.7
14.7
18.3
22.8
28.3
Power Input
5.6
5.8
6.1
6.3
6.5
6.8
7.0
7.2
1.42
12.8
Capacity
8.6
10.2
12.2
14.7
17.7
21.4
25.8
31.3
Power Input
4.3
4.6
4.8
5.0
5.3
5.5
5.8
6.0
21.1
Capacity
7.6
9.2
11.2
13.7
16.7
20.4
24.8
30.3
Power Input
5.1
5.3
5.6
5.8
6.1
6.3
6.5
6.8
26.7
Capacity
6.5
8.1
10.1
12.6
15.6
19.3
23.7
29.2
Power Input
5.5
5.7
6.0
6.2
6.4
6.7
6.9
7.2
1.77
12.8
Capacity
10.0
11.6
13.6
16.1
19.1
22.8
27.2
32.7
Power Input
4.5
4.7
4.9
5.2
5.4
5.6
5.9
6.1
21.1
Capacity
8.9
10.6
12.6
15.1
18.1
21.7
26.2
31.7
Power Input
5.2
5.5
5.7
5.9
6.2
6.4
6.7
6.9
26.7
Capacity
7.8
9.5
11.5
14.0
17.0
20.6
25.1
30.6
Power Input
5.6
5.9
6.1
6.3
6.6
6.8
7.0
7.3
THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (kW)